Serial Interface Manual
•
TLS2 Monitoring Systems
Part No. 577013-767, Revision H
145
Function Code:
A13
Version 1
Function Type:
Probe Long Term Average Buffers
Command Format:
Display:
<SOH>IA13TT
Computer:
<SOH>iA13TT
Typical Response Message, Display Format:
<SOH>
IA1301
22-05-01 15:13
TANK 1 REGULAR UNLEADED MAG NUMBER OF SAMPLES = 424
569.000 13584.000 13584.000 13584.000 13584.000 13585.000 13585.000 13584.000
13584.000 13585.000 13584.000 40000.000 21993.000 21993.000 21993.000 21993.000
21993.000 21993.000 40000.000
<ETX>
Typical Response Message, Computer Format:
<SOH>iA13TTYYMMDDHHmmTTpPPSSSSNNFFFFFFFF...
TTpPPSSSSNNFFFFFFFF...&&CCCC<ETX>
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
TT - Tank Number (Decimal, 00 = all)
3.
p - Product Code (single ASCII character, from 20 Hex - 7E Hex)
4.
PP - Probe Type:
00 - Unknown (no further data follows for this probe)
03 - MAG
5.
SSSS - Number of Samples (Hex)
6.
NN - Number of eight character Data Fields to follow (Hex)
7.
FFFFFFFF - Probe Data (ASCII Hex IEEE float)
8.
&& - Data Termination Flag
9.
CCCC - Message Checksum