Serial Interface Manual
•
TLS2 Monitoring Systems
Part No. 577013-767, Revision H
30
Function Code:
206
Version 1
Function Type:
In-Tank Alarm History Report
Command Format:
Display:
<SOH>I206TT
Computer:
<SOH>i206TT
Typical Response Message, Display Format:
<SOH>
I20601
22-05-01 14:57
STATION HEADER 1....
STATION HEADER 2....
STATION HEADER 3....
STATION HEADER 4....
TANK ALARM HISTORY
TANK 1 REGULAR UNLEADED
PROBE OUT 19-03-01 23:36
<ETX>
Typical Response Message, Computer Format:
<SOH>i206TTYYMMDDHHmmTTnnYYMMDDHHmmaaaa...
TTnnYYMMDDHHmmaaaa...&&CCCC<ETX>
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
TT - Tank Number (Decimal, 00 = all)
3.
nn - Number of alarms in history for tank (Decimal, 00 = none)
4.
YYMMDDHHmm - Date and time alarm occurred
5.
aaaa - Type of alarm:
0003 = Tank High Water Alarm
0004 = Tank Overfill Alarm
0005 = Tank Low Product Alarm
0008 = Tank Invalid Fuel Level Alarm
0009 = Tank Probe Out Alarm
000B = Tank Delivery Needed Warning
000C = Tank Maximum Product Alarm
000D = Tank Gross Leak Test Fail Alarm
000E = Tank Periodic Leak Test Fail Alarm
000F = Tank Annual Leak Test Fail Alarm
001B = Tank Cold Temperature Warning
6.
&& - Data Termination Flag
7.
CCCC - Message Checksum