Serial Interface Manual
•
TLS2 Monitoring Systems
Part No. 577013-767, Revision H
153
Function Code:
A31
Version 6
Function Type:
Multipoint Tank Chart Report
Command Format:
Display:
<SOH>IA31TT
Computer:
<SOH>iA31TT
Typical Response Message, Display Format:
<SOH>
IA3101
AUG 22, 2011 3:12 PM
MULTIPOINT TANK CHART
TANK 1: SUPER DUPER
HEIGHT VOLUME HEIGHT VOLUME HEIGHT VOLUME
MM LITERS MM LITERS MM LITERS
------------------------------------------------------------------------
0 0.000 480 4800.000 960 9600.000
10 100.000 490 4900.000 970 9700.000
20 200.000 500 5000.000 980 9800.000
30 300.000 510 5100.000 990 9900.000
40 400.000 520 5200.000 1000 10000.000
50 500.000 530 5300.000 1010 10100.000
60 600.000 540 5400.000 1020 10200.000
: : : : : :
: : : : : :
: : : : : :
<ETX>
Typical Response Message, Computer Format:
<SOH>iA31TTYYMMDDHHmmTTnnnnhhhhhhhhhhhhhhhhVVVVVVVVVVVVVVVV...
hhhhhhhhhhhhhhhhVVVVVVVVVVVVVVVV&&CCCC<ETX>
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
TT - Tank Number (Decimal, 00 = all)
3.
nnnn - Number of points to follow, (ASCII Hex)
4.hhhhhhhhhhhhhhhh- Height, ASCII-HEX Double Float, mm or inches
5.VVVVVVVVVVVVVVVV- Volume, ASCII-HEX Double Float, liters or gallons
6.
&& - Data Termination Flag
7.
CCCC - Message checksum