Serial Interface Manual
•
TLS2 Monitoring Systems
Part No. 577013-767, Revision H
138
Function Code 905 Notes:
(Continued)
9.
nn - number of 2 byte values to follow (Hex)
10.
AA - PERIODIC IN-TANK TESTS (00 = DISABLE, 01 = ENABLE)
11.
BB - ANNUAL IN-TANK TESTS (00 = DISABLE, 01 = ENABLE)
12.
CC - CSLD (00 = DISABLE, 01 = ENABLE)
13.
DD - BIR (00 = DISABLE, 01 = ENABLE)
14.
EE - FUEL MANAGER (00 = DISABLE, 01 = ENABLE)
15.
FF - PRECISION PLLD (00 = DISABLE, 01 = ENABLE)
16.
GG - TANKER LOAD (00 = DISABLE, 01 = ENABLE)
17.
HH - 0.2 GPH PLLD (00 = DISABLE, 01 = ENABLE)
18.
II - PRECISION PLLD ON DEMAND (00 = DISABLE, 01 = ENABLE)
19.
JJ - SPECIAL 3-TANK/LINE CONSOLE (00 = DISABLE, 01 = ENABLE)
20.
nnnnnn-vvv-r - SEM Info 3 parts, if none "NO SOFTWARE MODULE"
21.
nnnnnn - SEM number (ASCII text string)
22.
vvv - SEM Software version number (ASCII text string)
23.
r - SEM Software revision level (ASCII text string)
24.
&& - Data Termination Flag
25.
CCCC - Message Checksum