Serial Interface Manual
•
TLS2 Monitoring Systems
Part No. 577013-767, Revision H
92
Function Code:
611
Version 1
Function Type:
Set Tank Leak Test Type & Start Time
Command Format:
Inquire:
Display:
<SOH>S611TTDDRMYYMMDDHHmm<CR> (if M = 1)
<SOH>I611TT
MMWDHHmm<CR> (if M = 2)
WDHHmm<CR> (if M = 3)
DHHmm<CR> (if M = 4)
HHmm<CR> (if M = 5)
<CR> (if M = 6)
<CR> (if M = 7)
Computer:
<SOH>s611TTDDRMYYMMDDHHmm<CR> (if M = 1)
<SOH>i611TT
MMWDHHmm<CR> (if M = 2)
WDHHmm<CR> (if M = 3)
DHHmm<CR> (if M = 4)
HHmm<CR> (if M = 5)
<CR> (if M = 6)
<CR> (if M = 7)
Typical Response Message, Display Format:
<SOH>
I61101
22-05-01 15:09
LEAK TEST METHOD
TEST ON DATE : TANK 1
DISABLED
START TIME : DISABLED
TEST RATE : 0.20 GAL/HR
DURATION : 2 HOURS
TST EARLY STOP:DISABLED
<ETX>
Typical Response Message, Computer Format:
<SOH>i611TTYYMMDDHHmmTTDDRMYYMMDDHHmm (if M = 1)
MMWDHHmm (if M = 2)
WDHHmm (if M = 3)
DHHmm (if M = 4)
HHmm (if M = 5)
(none) (if M = 6)
(none) (if M = 7)
TTDDRMYYMMDDHHmm&&CCCC<ETX> (if M = 1)
MMWDHHmm&&CCCC<ETX> (if M = 2)
WDHHmm&&CCCC<ETX> (if M = 3)
DHHmm&&CCCC<ETX> (if M = 4)
HHmm&&CCCC<ETX> (if M = 5)
&&CCCC<ETX> (if M = 6)
&&CCCC<ETX> (if M = 7)
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
TT - Tank Number (Decimal, 00 = all)
3.
DD - Leak test Duration in hours (2 <= DD <= 24)
4.
R - Leak test Rate (0 = 0.2, 1 = 0.1)