Serial Interface Manual
•
TLS2 Monitoring Systems
Part No. 577013-767, Revision H
19
Function Code 111 Notes:
(Continued)
Typical Response Message, Computer Format:
<SOH>i11100YYMMDDHHmmAAccNNTTSSYYMMDDHHmm...
AAccNNTTSSYYMMDDHHmm&&CCCC<ETX>
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
AA - Alarm/Warning Category:
00 - All Functions Normal
02 - Tank Alarm
14 - Auto-Dial Alarm
3.
cc - Sensor Category
00 - Unused
4.
NN - Alarm Type Number:
- If AA is 02 and NN is:
03 = Tank High Water Alarm
04 = Tank Overfill Alarm
05 = Tank Low Product Alarm
08 = Tank Invalid Fuel Level Alarm
09 = Tank Probe Out Alarm
11 = Tank Delivery Needed Warning
12 = Tank Maximum Product Alarm
13 = Tank Gross Leak Test Fail Alarm
14 = Tank Periodic Leak Test Fail Alarm
15 = Tank Annual Leak Test Fail Alarm
27 = Tank Cold Temperature Warning
- If AA is 14 and NN is:
02 = Autodial Failed Alarm
5.
TT - Tank/Sensor Number
6.
SS - Alarm State
01 = Alarm cleared
02 = Alarm occurred
7.
YYMMDDHHmm - Date/Time Alarm state occurred
8.
&& - Data Termination Flag
9.