Serial Interface Manual
•
TLS2 Monitoring Systems
Part No. 577013-767, Revision H
26
Function Code:
202
Version 1
Function Type:
In-Tank Delivery Report
Command Format:
Display:
<SOH>I202TT
Computer:
<SOH>i202TT
Typical Response Message, Display Format:
<SOH>
I20201
22-05-01 14:56
STATION HEADER 1....
STATION HEADER 2....
STATION HEADER 3....
STATION HEADER 4....
DELIVERY REPORT
TANK 1 REGULAR UNLEADED
INCREASE DATE TIME VOLUME TC VOLUME WATER TEMP HEIGHT
END: 21-05-01 15:14 3231 3194 0.00 76.14 48.27
START: 21-05-01 15:05 1244 1231 0.00 73.89 24.40
AMOUNT: 1987 1963
<ETX>
Typical Response Message, Computer Format:
<SOH>i202TTYYMMDDHHmmTTpddYYMMDDHHmmYYMMDDHHmmNNFFFFFFFF...
TTpddYYMMDDHHmmYYMMDDHHmmNNFFFFFFFF...&&CCCC<ETX>
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
TT - Tank Number (Decimal, 00 = all)
3.
p - Product Code (single ASCII character, from 20 Hex - 7E Hex)
4.
dd - Number of Deliveries to follow (Decimal, 00 if no data
available for this tank)
5.
YYMMDDHHmm - Starting Date/Time
6.
YYMMDDHHmm - Ending Date/Time
7.
NN - Number of eight character Data Fields to follow (Hex)
8.
FFFFFFFF - ASCII Hex IEEE float:
1. Starting Volume
2. Starting TC Volume
3. Starting Water
4. Starting Temp
5. Ending Volume
6. Ending TC Volume
7. Ending Water
8. Ending Temp
9. Starting Height
10. Ending Height
9.
&& - Data Termination Flag
10.
CCCC - Message Checksum