E5
−
H High Performance Universal Inverter User Manual
98 Chapter
6
Parameter
Description
Display of operational panel
Unit place
Action when power failure
0: Mains loss save;
1: Zero clearing upon mains loss
Tens place
Action upon stop
0: Maintained upon stop;
1: Reset when deceleration to stop;
2: Reset when standby
Hundreds
place
Terminal UP/DN regulation setting
0: Only enabled when main reference is
P0.05 open loop digital frequency setting;
1: Enabled during adjustment;
2: Disabled during adjustment
Thousands
place
0: With integral function;
1: Without integral function
Pb.10 and Pb.11 are the same as the usage of operational panel / . For functions of terminal
∧ ∨
UP/DN,
refer to instructions of P5.00~P5.06.
Display of operational panel
Unit place
Arrive continuous running time:
0: Continue running; 1: Stop and alarm
Tens place
Arrive summation running time:
0: Continue running; 1: Stop and alarm
This function code use for inverter automatic stop and alarm or continue running once running time
reaches the user preset time. The function code Pb.13, Pb.14 defaults to 0, not timing.
From the inverter to respond the running command, continuous running time reaches continuous running
time reference (Pb.13), can output this signal through Y1 terminal or relay terminal , and the Y1 terminal
function number (P7.00) or relay terminal function number (P7.02) set to 18: arrive continuous running
time.
From the inverter power on, running time reaches summation running time reference (Pb.14), can output
this signal through Y1 terminal or relay terminal, and the Y1 function number (P7.00) or relay terminal
function number (P7.02) set to 17: arrive summation running time.
Note:
◆
Summation running time and continuous running time will be reset to 0 if power off.
◆
Continuous running time will be reset to 0 in stopping status even power on. If continuous running
time output signal is enabled, will become disabled in stopping status and be reset to 0.
◆
Summation running time will not be reset to 0 in stopping status. If summation running time output
signal is enabled, will become disabled in stopping status and be reset to 0.
Pb.15
Restart automatically after power resumes normal
0~1(0)
Pb.16
Waiting time for restart
0.0~20.0 s(0.5s)
Pb.12
Action setting after arrive fererence running time
00~11(00)
Pb.13
Continuous running time reference
0.0~6553.5min(0.0min)
Pb.14
Summation running time reference
0.0~6553.5min(0.0min)