E5
−
H High Performance Universal Inverter User Manual
Chapter 5 List of Parameters
41
Function
code
number
Function code name
Factory
setting
Setting range Unit Property
Function code selection
User
setting
Group P3 Start/stop Parameter
P3.00
Startup mode
0
0 ~ 2
/
×
0: Normal startup;
1: Start after DC injection;
2: Catch a spinning motor
P3.01
DC injection current
0.0
0.0 ~ 120.0
%
×
Constant torque: 0.0 ~ 120.0% inverter
rated current
P3.02
DC injection time
0.00
0.00 ~ 30.00
s
×
0.00 ~ 30.00s
P3.03 Startup
frequency
0.0 or
0.50
0.00 ~ 60.00
Hz
×
0.00 ~frequency high limit the lower of
P0.13 and 60.00Hz
P3.04
Startup frequency
retention time
0.0
0.0 ~ 3600.0
s
×
0.0 ~ 3600.0s
P3.05
Stop mode
0
0 ~ 2
/
×
0: Deceleration to stop;
1: Coast to stop;
2: Deceleration to stop+DC braking
P3.06
DC braking initial
frequency
0.00
0.00 ~ 300.00
Hz
×
0.00 ~ 300.00Hz
P3.07
DC braking current
0.0
0.0 ~ 120.0
%
×
Constant torque: 0.0 ~ 120.0% inverter
rated current
Variable torque: 0.0 ~ 90.0% inverter
rated current
P3.08
DC braking time
0.00
0.0 0~ 30.00
s
×
0.00~ 30.00s
P3.09 Anti
−
reverse selection
1
0 ~ 1
/
×
0: Run reverse enabled;
1: Run reverse disabled
P3.10
Forward / reverse dead
zone time
0.0
0.0 ~ 3600.0
s
×
0.0 ~ 3600.0s
P3.11
Jog frequency
5.00
0.10 ~ 300.00
Hz
×
0.10 ~ 300.00Hz
P3.12
Jog acceleration time
6.0
0.1 ~ 60.0
s
×
0.1 ~ 60.0s
P3.13
Jog deceleration time
6.0
0.1 ~ 60.0
s
×
0.1 ~ 60.0s
Group P4 Multi
−
section Parameter
P4.00
V/F curve reference
0
0 ~ 6
/
×
0: Direct line;
1: Multi
−
section (P4.01 ~ P4.08);
2: Power of 1.2;
3: Power of 1.4;
4: Power of 1.6;
5: Power of 1.8;
6: Power of 2
P4.01
V/F frequency value F0
0.00
0.00 ~ 300.00
Hz
×
F0<F1
P4.02
V/F voltage value V0
0.0
0.0 ~ 100.0
%
×
0.0 ~ 100.0%
P4.03
V/F frequency value F1
0.00
0.00 ~ 300.00
Hz
×
F1<F2
P4.04
V/F voltage value V1
0.0
0.0 ~ 100.0
%
×
0.0 ~ 100.0%
P4.05
V/F frequency value F2
0.00
0.00 ~ 300.00
Hz
×
F2<F3
P4.06
V/F voltage value V2
0.0
0.0 ~ 100.0
%
×
0.0 ~ 100.0%
P4.07
V/F frequency value F3
0.00
0.00 ~ 300.00
Hz
×
F3< Motor basic frequency P0.15
P4.08
V/F voltage value V3
0.0
0.0 ~ 100.0
%
×
0.0 ~ 100.0%
P4.09
Acceleration time 1
20.0
0.1 ~ 3600.0
s
×
0.1 ~ 3600.0s
P4.10
Deceleration time 1
20.0
0.1 ~ 3600.0
s
×
0.1 ~ 3600.0s
P4.11
Acceleration time 2
20.0
0.1 ~ 3600.0
s
×
0.1 ~ 3600.0s
P4.12
Deceleration time 2
20.0
0.1 ~ 3600.0
s
×
0.1 ~ 3600.0s
P4.13
Acceleration time 3
20.0
0.1 ~ 3600.0
s
×
0.1 ~ 3600.0s
P4.14
Deceleration time 3
20.0
0.1 ~ 3600.0
s
×
0.1 ~ 3600.0s
P4.15
Multi
−
section digital
voltage reference 1
1.00
0.00 ~ 10.00
V
○
0.00
~
10.00V
P4.16
Multi
−
section digital
voltage reference 2
2.00
0.00 ~ 10.00
V
○
0.00
~
10.00V
P4.17
Multi
−
section digital
voltage reference 3
3.00
0.00 ~ 10.00
V
○
0.00
~
10.00V