H High Performance Universal Inverter User Manual
4
Chapter 1 Introduction to E5
−
H Series Inverter
Protection
function
Power supply undervoltage, overcurrent protection, overvoltage protection, interference protection,
abnormal comparison reference input, auto
−
tuning failure, module protection, heatsink overtemperature
protection, inverter overload protection, motor overload protection, peripheral protection, abnormal current
detection, output to ground short circuit, abnormal power failure during operation, abnormal input power,
output phase failure, abnormal EEPROM, relay suction pull-on anomaly, temperature sensor taking
sample anomaly, ab10V power supply output, abnormal analog input, motor overtemperature
(PTC), abnormal communication, abnormal version compatibility, abnormal copying, terminal mutual
exclusion detection failure, hardware overload protection
Efficiency
At rated power, 7.5kW and below power class
≥
93%, 45kW and below power class
≥
95%, 55kW and
above power class
≥
98%
Operating site
The inverter shall be mounted vertically in the electric control cabinet with
good ventilation. Horizontal or other installation modes are not allowed. The
cooling medium is the air. The inverter shall be installed in the environment
free from direct sunlight, dust, corrosive gas, combustible gas, oil mist, steam
and drip.
Ambient temperature
−
10 ~ +40ºC, derated at 40 ~ 50ºC, the rated output current shall be
decreased by 1% for every temperature rise of 1ºC
Humidity
5 ~ 95%, no condensing
Altitude
0 ~ 2000m, derated above 1000m, the rated output current shall be
decreased by 1% for every rise of 100m
Vibration
3.5mm,2~9Hz; 10 m/s
2
,9~200Hz; 15 m/s
2
,200~500Hz
Environment
Storage temperature
−
40~+70ºC