15: Inverter reports alarm
When the inverter is in the alarm status due to fault but does not stop, the signal is enabled.
17: Arrive summation running time
The signal is enabled when the inverter runs repeatedly and running time reaches the setting, and the
signal will be reset upon power-off. For details refer to Pb.14.
18: Arrive continuous running time
When the inverter running one time, the signal is enabled when running time reaches the setting, and the
signal will be reset if in stopping status. For details refer to Pb.13.
19: Output X1
The status of X1 terminal is output via the terminal Y, when X1 is enabled, the signal is enabled.
20: Output X2
The status of X2 terminal is output via the terminal Y, when X2 is enabled, the signal is enabled.
22: Zero current detection arrival
When the output current of the inverter is lower than the zero current detection width during operation,
the signal is enabled. Refer to P7.18 for details.
23: Stop command instruction
When the inverter is in the stop or standby status, the signal is enabled.
32: Sleeping state indication
When the inverter is in sleeping status, the signal is enabled.
12, 16, 21, 24 ~ 31 and 33~47: Reserved
The definition table of multifunctional analog outpu is as follows:
Function setup
Output signal selection
Definition of analog output range
48
Output frequency
Maximum frequency P0.11 corresponds to 10V/20mA.
49
Setup frequency
Maximum frequency P0.11 corresponds to 10V/20mA.
50
Output current
Two times rated current of inverter corresponds to 10V/20mA.
51
Motor current
Two times rated current of motor corresponds to10V/20mA
52
Output torque
Two times rated torque of motor corresponds to 10V/20mA.
53
Output voltage
Two times maximum output voltage P0.12 corresponds to 10V/20mA.
54
Bus voltage
1000V corresponds to 10V/20mA
55
AI1
10V corresponds to 10V/20mA; 20mA corresponds to 5V/10mA.
56 AI2
Same
as
AI1
57~58 Reserved
59
Output power
2 times rated output power of motor corresponds to 10V/20mA.
60
Host computer percentage 10000 corresponds to10V/20mA.
61
Heatsink temperature
0 to 100 corresponds to 0 to 10V/20mA
℃
62
Output frequency 2
Maximum frequency P0.11 corresponds to 10V/20mA
Note:
1. Output frequency indicate the output frequency of inverter, Output frequency 2 indicate the frequency