Chapter 6 Parameter Description
97
Display of operational panel
Unit place
Action when power failure
0: mains loss save;
1: reset upon mains loss
Tens place
Action when stop
0: Maintain when stop;
1: Reset clear when deceleration or stop;
2: Reset during standby
Hundreds
place
Operational panel
∧
/
∨
regulation setting
0: Only enabled when main reference is
P0.05 open loop digital frequency setting
1: Enabled during adjustment;
2: Disabled during adjustment
Thousands
place
0: With integral function;
1: Without integral function
Unit place: Action upon mains loss
0: After setting frequency by operational panel
∧
/
∨
adjustment, operational panel
∧
/
∨
adjustment
volume will be recorded automatically after power to the inverter is cut off.
1: After setting frequency by operational panel
∧
/
∨
adjustment, operational panel
∧
/
∨
adjustment
volume will be cleared automatically after power to the inverter is cut off.
Tens place: Action during stopping process
0: After the inverter stops, adjustment volume of
∧
/
∨
on operational panel keeps unchanged.
1: After the inverter stops, adjustment volume of
∧
/
∨
on operational panel will be cleared after carrying
out stop command.
2: After the inverter stops, adjustment volume of
∧
/
∨
on operational panel is cleared under the stop
status. Frequency cannot set by
∧
/ under the stop status.
∨
Hundreds place: Setting of / on operational panel
∧ ∨
0: Only enabled when the main reference is P0.05 open loop digital frequency setting (P0.04=0).
1: Enabled under all frequency reference modes (P0.04 not specified).
2: Operational panel adjustment / disabled.
∧ ∨
Thousands place: Setting of / on operational panel
∧ ∨
0: With integral function. When the operation panel / adjustment is used to set the frequency, the
∧ ∨
consistent adjustment in one direction has integral effect. The step length of adjustment starts from
0.01Hz, after every 10 times of adjustment, the step length will be increased by 10 times, and the
maximum step length of adjustment is 1.00Hz.
1: Without integral function. When the operation panel / adjustment is used to set the frequency, the
∧ ∨
step length of the adjustment is fixed to 0.1Hz.
Note: When operating under process closed loop PID, the closed loop reference also can be adjusted
with operational panel / . Then adjustment volume of / is regarded as analog superimposed upon
∧ ∨
∧ ∨
closed loop reference. The minimum step size is 1mV.
Pb.10
Terminal UP/DN digital regulating frequency control
0000~1221(0001)
Pb.11
Terminal UP/DN integral rate
0.1~50.0 s(2.0s)