H High Performance Universal Inverter User Manual
Chapter 6 Parameter Description
53
Chapter 6 Parameters Description
6.1 Basic Function Parameter (Group P0)
This function is used to prevent the irrelevant personnel from querying and changing the parameters, so
as to protect the safety of the inverter parameters.
0000: No password protection: All the parameters in Zone P can be queried and changed (If P0.01=1,
the change to parameters is disabled), and no password is set upon inverter delivery.
Set password:
Enter four digits as user password, and press PRG key for confirmation. Repeat this operation once.
Change password:
Press PRG key to enter the password verification status, and 0.0.0.0. is displayed. Enter correct
password, and it enters parameter editing status. Select P0.00 (parameter P0.00 displayed as 0000).
Input new password and press PRG key for confirmation. Set the same password for P0.00 twice.
When “P.Set” is displayed, the new password is successfully set.
Cancel password:
Press PRG key to enter the password verification status, and 0.0.0.0. is displayed. Enter correct user
password to enter the parameter editing status, check if P0.00 is 0000. Press PRG key for confirmation,
and set P0.00=0000 again, and then “P.Clr” is displayed and the password is cancelled.
Note: For the method for activating the password, refer to 4.5 password operation.
This function is used to set the modification authority and initialization level of the parameters.
0: All the parameters are allowed for modification.
1: All the parameters are disallowed for modification.
2: Restore all the parameters in zone P to factory setting.
3. Restore all the parameters in zone P except for the motor parameters (group P9) to factory setting.
4: Restore all the P zone parameters and A zone parameters (user’s customized function code
display/hide zone) to factory settings.
5: Restore all the user parameters except for d group to factory settings.
Note: After the parameters are initialized, the password set by the user will be automatically reset.
Set this function, and the operation panel will display the function code parameters according to the
actual need of the user to improve the work efficiency.
0: Basic menu mode: The operation panel can display all the parameters.
1: Fast menu mode: The operation panel only displays the fast parameters defined by the manufacturer.
When the basic functions of the inverter are used, this menu mode shall be set.
2: Menu mode of non
−
factory setting function code: The operation panel only displays the parameters
P0.00
User password
0~FFFF(0)
P0.01
Function code protection
0~5(0)
P0.02
Function code display
0~3(0)