Chapter 2 Inverter Installation
9
Chapter 2 Inverter Installation
2.1 Environment for Product Installation
Do not install the inverter in the sites with oil mist, metal powder and dust.
Do not install the inverter in the sites with hazardous gas and liquid, and corrosive, combustible and
explosive gas.
Do not install the inverters in salty sites.
Do not install the inverter in the sites with direct sunlight.
Do not mount the inverter on the combustible materials, such as wood.
Keep the drilling scraps from falling into the inverter during the installation.
Mount the inverter vertically in the electric control cabinet, mount the cooling fan or air conditioner
to prevent the ambient temperature from rising to above 45 ºC.
For the sites with adverse environment, it is recommended to mount the inverter heatsink outside
the cabinet.
2.2 Mounting Direction and Space
In order not to reduce the inverter cooling effect, the inverter must be mounted vertically, and certain
clearance must be maintained, as shown in Figure 2
−
1 and Figure 2
−
2.
Figure 2
−
1 Mounting direction and clearance E5
−
H
−
4T7.5G and below power class
Air circulation position
Air circulation position
Above 120mm
Above 120mm
Air circulation position
Air circulation position
Above 120mm
Above 120mm
Above 30mm
Above 30mm