7. Case Study of Modbus Communication Control
Start No.1 inverter to perform forward running, and set the rotation velocity to 50.00Hz (indicating 5,000 internally) as
per the following commands:
Address
Function
code
Register
Address
Number
Bytes
Register
Contents
Check Sum
Request 0x01 0x10 0x8000 0x0002
0x04 0x0001,0x1388
0xCEFF
Response 0x01
0x10 0x8000 0x0004
None
None
0xE80A
Read the operating frequency of No.1 inverter and the response operating frequency of the inverter is 50.00Hz:
Address
Function
code
Register
Address
Number Bytes
Register
Contents
Request 0x01 0x03 0x8136
0x0001
None
0x4C38
Response 0x01
0x03
None
0x02
0x1388
0xB512
No.1 inverter stops in the default mode:
Address
Function
code
Register
Address
Register Contents
Check Sum
Request 0x01 0x06 0x8000
0x0000
0xA00A
Response 0x01
0x06
0x8000
0x0000
0xA00A
"
Note:
It needs to set P0.06 to 2 firstly.
8. Communication Network Construction
Connecting one inverter to the computer
Attached Figure 3 Connecting One Inverter to the Computer