E5
−
H High Performance Universal Inverter User Manual
76 Chapter
6
Parameter
Description
Since the using methods of curve 1 and curve 2 are identical, Curve 1 is described as an example here.
Both curve 1 and curve 2 can be used in process open loop analog frequency reference, and the running
frequency of the inverter can be determined by the analog values AI1 and AI2. The conversion
relationship between analog value and setup frequency is as shown in the figures below:
Figure 6
−
19 Corresponding percentage of input
analog value (voltage)
Figure 6
−
20 Corresponding percentage of input
analog value (current)
Figure 6
−
21 Setup frequency characteristics curve
(positive effect)
Figure 6
−
22 Setup frequency characteristics curve
(negative effect)
P6.01
Curve 1 input point A0
0.0 ~110.0 %(0.0%)
P6.02
Reference frequency f0 corresponding to curve 1 input point A0
0.00~ 300.00 Hz(0.00Hz)
P6.03
Curve 1 input point A1
0.0 ~110.0 %(100.0%)
P6.04
Reference frequency f1 corresponding to curve 1 input point A1
0.00 ~ 300.00 Hz(50.00Hz)
P6.05
Curve 2 input point A0
0.0 ~110.0 %(0.0%)
P6.06
Reference frequency f0 corresponding tocurve 2 input point A0
0.00 ~300.00 Hz(0.00%)
P6.07
Curve 2 input point A1
0.0 ~110.0 %(100.0%)
P6.08
Reference frequency f1 corresponding to curve 2 input point A1
0.00 ~ 300.00 Hz(50.00Hz)