E5
−
H High Performance Universal Inverter User Manual
38
Chapter 5 List of Parameters
Chapter 5 List of Parameters
Meanings of Each Item in Function Code Parameter Table
Item
M e a n i n g s
Function code number
The number of function code, such as P0.00
Function code name
The name of function code, which explains the function code’s meanings.
Factory setting
Restore the settings of the function code after the inverter is delivered (see P0.01).
Setting range
The value from minimum value to maximum value that can be set to this function code.
Unit
V: Voltage; A: Current; ºC: Celsius degree;
Ω
: Ohm; mH: Milli
−
henry; rpm: Rotating speed; %:
Percentage; bps: baud rate; Hz, kHz: Frequency; ms, s, min, h, kh: Time; kW: Power; Mpa:
Pressure; /: No unit
Property
○
: This function code can be changed during operation; ×: This function code can only be
changed during stopping process; *: The setting of this function code is read
−
only and cannot
be changed.
Function code
selection
Function code parameter setting list
User setting
Used for recording parameters by user
Note:
◆
E5 series inverter built
−
in multi fan and pump control mode to realize customsized energy saving
requirement. For details, refer to the descriptions of function code of Pb.21 and Pb.22.
◆
E5 series inverter built
−
in constant pressure close loop control and sleeping function. For details,
refer to the descriptions of function code of group H0.
5.1 List of Basic Menu Function Codes
Function
code
number
Function code name
Factory
setting
Setting range Unit Property
Function code selection
User
setting
Group P0 Basic Function Parameter
P0.00 User
password
0000
0
~FFFF /
○
0000: No password;
Other: Password protection
P0.01
Function code
protection
0
0 ~ 5
/
×
0: All the parameters can be modified;
1: All the parameters cannot be
modified;
2: Restore parameters in zone P to
factory settings;
3: Restore parameters in zone P to
factory settings; (except for P9 group)
4: Recover the parameters in zone P
and zone A to factory settings;
5: Recover all the parameters to
factory settings. (except for d group)
P0.02
Function code display
0
0 ~ 3
/
○
0: Basic menu mode
1: Fast menu mode
2: Menu mode of non
−
factory setting
value function codes;
3: Menu mode of last changed 10
function codes;
P0.03
Control operation mode
0
0 ~ 1
/
×
0: Process open loop control;
1: Analog value feedback process
close loop control
P0.04
Open loop main
reference mode
0
0 ~ 4
/
×
0: Open loop digital frequency
reference (P0.05);
1: AI1 analog value reference;
2: AI2 analog value reference