78 Chapter
6
Parameter
Description
P6.21 is used to select functions of AI1, AI2 terminals. Since the using methods of AI1and AI2 are
identical, AI1 is described as an example here:
0: Open loop frequency or analog close loop rotation velocity reference: AI1 analog input is converted
into setup frequency via the analog curve.
1~4: Reserved
5: Motor temperature feedback: It is used together with P9.17 sensor protection threshold to report motor
thermal protection alarm.
6: Reserved
Note: If the analog channel function is set to a non
−
zero value, please make sure that different analog
channels have different functions.
In field applications, the analog values input via AI1, AI2 usually have certain interference signals. It can
amplify the setup value of AI filter time properly to improve the anti
−
interference capability of the terminal
input. However, the longer the filtering time of the terminal is, the longer the delay for the response to the
action of the terminal is.
6.8 Multi
−
function Output Parameter (Group P7)
Y1 and relay terminals can be defined as multifunctional digital signal output. AO1 and AO2 terminals
can be defined as multifunctional analog value output, and the analog value type (0 ~ 10V/0 ~ 20mA) can
be selected via the jumper.
The definition table of multifunctional digital signal output is as follows:
Function setup
Meaning
Function setup
Meaning
0
Signal indicating that the inverter is
running (RUN)
1
Frequency arrival signal (FAR)
2
Frequency level detection signal
1(FDT1)
3
Frequency level detection signal
2(FDT2)
4
Pre
−
warning signal indicating inverter
or motor overload (OL)
5
Stop and lock due to under voltage
(LU)
6
Stop due to external failure (EXT)
7
Frequency high limit(FHL)
8
Frequency low limit(FLL)
9
Inverter is running at zero speed
10
Preset counting value action
11
Counting value arrival action
12
Reserved
13
Inverter ready for operation (RDY)
14
Inverter failure
15
Inverter reports alarm
16 Reserved
17 Arrive
summation
running
time
18
Arrive continuous running time
19
Output X1
P6.22
AI1 filtering time
0.000~1.000 s(0.004s)
P6.23
AI2 filtering time
0.000~1.000 s(0.004s)
P7.00
Y1 terminal output function selection
0 ~ 47(0)
P7.02
Relay terminal output function selection
0 ~47(14)
P7.03
AO1 terminal output function selection
48~ 71(48)
P7.04
AO2 terminal output function selection
48 ~ 71(49)