vacon • 45
Parameter description
4
Figure 6. Start/Stop logic = 1.
Explanations:
Selection
number
Selection name
Note
1
Start sign 1: Start Forward
Start sign 2: Reverse
The function takes place when the contacts are
closed.
1
Start sign 1 activates causing the output fre-
quency to rise. The motor runs forward.
7
Run enable signal is set to FALSE, which drops
the frequency to 0. The run enable signal is con-
figured with parameter P4.7.
2
Start sign 2 activates which causes the direction
to start changing (FWD to REV).
8
Run enable signal is set to TRUE, which causes
the frequency to rise towards the set frequency
because Start sign 1 is still active.
3
Start sign 2 is inactivated which causes the
direction to start changing (REV to FWD)
because Start sign 1 is still active.
9
Keypad stop button is pressed and the frequency
fed to the motor drops to 0. (This signal only
works if P2.22 Keypad stop button = Yes)
4
Also Start sign 1 inactivates and the frequency
drops to 0.
10
Pushing the Start button on the keypad has no
effect on the drive status.
5
Despite the activation of Start sign 2, the motor
does not start because Start sign 1 is inactive.
11
The drive is stopped again with the stop button
on the keypad.
6
Start sign 1 activates causing the output fre-
quency to rise again. The motor runs forward
because Start sign 2 is inactive.
12
The attempt to start the drive through pushing
the Start button is not successful even if Start
sign 1 is inactive.
t
Output
frequency
FWD
REV
Start sgn 2
Start sgn 1
Run enable
Set frequency
Set frequency
0 Hz
Keypad stop
button
Keypad start
button
1
2
3
4
6
7
8
9
10
11
12
5