Description of Groups
vacon • 36
Service support: find your nearest Vacon service center at www.vacon.com
3
3.3.14
Group Flow meter: Menu PAR G15
Code
Parameter
Min
Max
Unit
Default
ID
Description
P15.1
Flowmeter signal
0
3
0
1958
Selections:
0 = not used
1 = Digital pulse
2 = AI1
3 = AI2
P15.2
Flow at max anlg signal
0
65500
litres/
min
1000
1960
Considered when flow meter
signal is from analogue signal
(AI1 or AI2). It is the flow leve at
maximum analogue signal.
P14.3
Pulse output volume
0
10000
litres/
pulse
100
1954
Considered when flow meter
signal is from digital input. It is
the total volume of water for
each pulse.
Table 20. Flow meter parameters.