vacon • 75
Parameter description
4
P12.11 PID
E
RROR
LIMIT
If lower than 100%, determines a limit on max error. Useful to avoid excessive reaction at mo-
tor startup.
P12.12 S
LEEP
FREQUENCY
This function will put the drive into sleep mode if the setpoint is reached and the output fre-
quency stays below the sleep limit for a longer time than that set with the Sleep Delay (P12.13).
This means that the start command remains on, but the run request is turned off. When the
PID error value goes below, or above, the wake-up level depending on the set acting mode
(P12.10) the drive will activate the run request again if the start command is still on.
P12.13 S
LEEP
TIME
DELAY
Time of working at minimum frequency, before entering sleep condition.
P12.14 W
AKE
UP
LIMIT
The drive exits from sleep if the error exceeds this value. Direction of regulation (P12.10) is in-
ternally considered.
P12.15 F
EEDBACK
S
UPERV
. R
ESPONSE
Response to feedback supervision:
0 = No action
1 = Alarm
2 = Fault
P12.16 M
IN
FEEDBACK
LEVEL
P12.17 M
IN
FEEDBACK
TIME
P12.18 M
AX
FEEDBACK
LEVEL
P12.19
M
AX
FEEDBACK
TIME
These parameters manage the supervision of the PID actual value (feedback).
If the difference between setpoint and actual value stays then lower than P12.16 for the time in
P12.17, the drive response is according to P12.15. If P12.15 is 2, this activates fault F58.
If the difference between setpoint and actual value stays then higher than P12.18 for the time
in P12.19, the drive response is according to P12.15. If P12.15 is 2, this activates fault F59.