vacon • 33
Description of Groups
3
3.3.12
Group PID Control: Menu Par G12
Code
Parameter
Min
Max
Unit
Defau
lt
ID
Description
P12.1
Setpoint source
0
3
0
332
0 = PID setpoint 1/2
1 = AI1
2 = AI2
3 = Fieldbus
P12.2
PID setpoint 1
0.0
100.0
%
50.0
167
Fixed setpoint 1
P12.3
PID setpoint 2
0.0
100.0
%
50.0
168
Fixed setpoint 2
P12.4
Feedback source
0
3
0
334
0 = AI2
1 = AI1
2 = Fieldbus
3 = AI1- AI2
P12.5
Feedback minimum
0.0
50.0
%
0.0
336
Value at minimum signal
P12.6
Feedback maximum
10.0
300.0
%
100.0
337
Value at maximum signal
P12.7
PID controller P gain
0.0
1000.0
%
100.0
118
If the value of the parameter is set
to 100% a change of 10% in the
error value causes the controller
output to change by 10%.
P12.8
PID controller I-time
0.00
320.00
s
10.00
119
If this parameter is set to 1,00 sec-
ond a change of 10% in the error
value causes the controller output
to change by 10.00%/s.
P12.9
PID controller D-time
0.00
10.00
s
0.00
132
If this parameter is set to 1,00 sec-
ond a change of 10% in the error
value during 1.00 s causes the
controller output to change by
10.00%.
P12.10
Error value inversion
0
1
0
340
0 = Normal (Feedback < Setpoint -
> Increase PID output)
1 = Inverted (Feedback < Setpoint -
> Decrease PID output)
P12.11
PID error limit
0.0
100.0
%
100.0
1812
Limit on error
P12.12
Sleep frequency
0.00
200.0
Hz
0.00
1016
Drive goes to sleep mode when the
output frequency stays below this
limit for a time greater than that
defined by parameter P12.13.
P12.13
Sleep time delay
0
3600
s
30
1017
The minimum amount of time the
frequency has to remain below the
Sleep level before the drive is
stopped.
P12.14
Wake-up limit
0.0
100.0
%
5.0
1018
Defines the level for the PID feed-
back value wake-up.
P12.15
Feedback Superv.
Response
0
2
2
1894
Response to feedback supervision:
0 = No action
1 = Alarm
2 = Fault
P12.16
Min feedback level
0.0
100.0
%
50.0
1895
Min variation between setpoint
and feedback to activate the Feed-
back Superv. Response
Table 18. PID control group.