Description of Groups
vacon • 30
Service support: find your nearest Vacon service center at www.vacon.com
3
P9.8
Underload load curve
at nominal freq.
10.0
150.0
%
90.0
714
This parameter gives the
value for the minimum
torque allowed when the out-
put frequency is above the
field weakening point.
P9.9
Underload load curve
at min freq.
0.0
150.0
%
0.0
715
This parameter gives value
for the minimum torque
allowed with zero frequency.
P9.10
Underload time
1
300
m
20
716
This is the maximum time
allowed for an underload
state to exist.
P9.11
Thermal protection of
the motor
0
2
2
704
See P9.3
P9.12
Motor ambient
temperature
-20
100
°C
40
705
Ambient temperature in °C
P9.13
Motor cooling factor at
zero speed
0.0
150.0
%
40.0
706
Defines the cooling factor at
zero speed in relation to the
point where the motor is run-
ning at nominal speed with-
out external cooling.
P9.14
Motor thermal time
constant
1
200
min
45
707
The time constant is the time
within which the calculated
thermal stage has reached
63% of its final value.
P9.15
Response to fieldbus
fault
0
2
2
733
See P9.3
P9.17
Parameter lock
0
1
0
1805
Lock parameter editing.
0 = Edit enabled
1 = Edit disabled
P9.18
Response to STO
disable
0
3
1
1876
0 = No action
1 = Warning
2 = Fault, not stored in his-
tory menu
3 = Fault, stored in history
menu
P9.19
Response to input
phase fault
0
2
0
1877 See P9.3
P9.20
Input phase fault max
ripple
0
75
0
1893
Sensitivity of input phase
fault detector.
0 = internal value
1 = max sensitivity ->
75 = min sensitivity
P9.21
Motor temp initial
mode
0
2
0
1891
0 = start from minimum
1 = start from constant value
2 = start from last value
P9.22
Motor temp initial
value
0
100
%
33
1892
Initial value(P9.21 = 1) or fac-
tor for last previous
value(P9.21 = 2)
P9.23
UnderloadDetectMode
0
1
0
1950
0 = Motor Torque
1 = Flowmeter (transducer
defined by P15.1)
P9.24
Minimum Flow
1
65500
litres/
min
300
1951
Value to determine under-
load fault if P9.23 is 1