vacon • 85
Fault tracing
5
30
STO fault
Safe torque off signal does not
allow drive to be set as ready
Reset the fault and restart.
Should the fault re-occur, con-
tact the distributor near to you.
35
Application
error
0
Firmware Interface version
between Application and Control
not matching
Load a compatible application.
Please contact your closest
Vacon representative.
1
Application software flash error
Reload Application
2
Application header error
Load a compatible application.
Please contact your closest
Vacon representative.
41
IGBT temp
IGBT temperature (UnitTempera-
ture + I2T) too high
Check loading.
Check motor size.
Make identification run.
50
4 mA fault
(Analog input)
Selected signal range: 4...20 mA
(see Application Manual)
Current less than 4 mA
Signal line broken detached
The signal source is faulty
Check the analog input’s cur-
rent source and circuit.
51
External fault
Error message on digital input.
The digital input was programmed
as an input for external error mes-
sages. The input is active.
Check the programming and
check the device indicated by
the error message.
Check the cabling for the
respective device as well.
52
Keypad Communication
fault
The connection between the con-
trol keypad and the frequency con-
verter is broken.
Check keypad connection and
keypad cable.
53
Fieldbus communication
fault
The data connection between the
fieldbus master and fieldbus board
is broken
Check installation and fieldbus
master.
54
Fieldbus Interface error
Defective option board or slot
Check board and slot.
55
Wrong run command
Wrong run alarm and stop com-
mand
Run forward and backward are
activated at the same time
56
Temperature
Temperature fault
Board OPTBH is installed and
measured temperature is above
(or below) the limit
57
Identification
Identification alarm
Motor identification has not
been successfully completed
58
Feedback Supervision
Min
The variation between setpoint and
feedback is lower than min value
P12.16 for the time P12.17
Check settings and parameters
of this protection.
59
Feedback Supervision
Max
The variation between setpoint and
feedback is higher than max value
P12.18 for the time P12.19
Check settings and parameters
of this protection.
Fault
code
Fault name Subcode
Possible cause
Remedy
Table 29. Fault codes and descriptions.