vacon • 81
Parameter description
4
4.14
Flow meter
This group is to setup the flow meter sensor.
P15.1 F
LOW
METER
SIGNAL
Flow meter selection:
0: Not used
1: Digital pulse
2: AI1
3: AI2
P15.2
F
LOW
AT
MAX
ANLG
SIGNAL
Considered when flow meter signal is from analogue input. It is the flow value at maximum sig-
nal level of the analogue input.
P15.3 P
ULSE
OUTPUT
VOLUME
Considered when flow meter signal is from digital input. It is the total water volume for each
pulse.