Parameter description
vacon • 68
Service support: find your nearest Vacon service center at www.vacon.com
4
P9.18
R
ESPONSE
TO
STO
DISABLE
0: No action
1: Warning
2: Fault, not stored in history
3: Fault, stored in history
Safe Torque Off disabled.
P9.19
R
ESPONSE
TO
INPUT
PHASE
FAULT
0: No action
1: Warning
2: Fault
Input phase missing.
P9.20
I
NPUT
PHASE
FAULT
MAX
RIPPLE
Sensitivity for input phases detection:
0: internal value (default)
1-75: sensitivity from maximum(1) to minimum (75)
P9.21
M
OTOR
TEMP
INITIAL
MODE
Setting of estimated motor temperature at power on
0: initialized at minimum value
1: initialized at constant value from P9.22
2: initialized at last previous value, with P9.22 used as factor
P9.22
M
OTOR
TEMP
INITIAL
VALUE
If P9.21= 1, motor temperature is initialized with this value.
If P9.21= 2, motor temperature is initialized with last previous value, multiplied by this value
as% factor.
P9.23 U
NDERLOAD
D
ETECT
M
ODE
This parameter selects the underload protection mode:
0: Motor torque (standard sensorless mode based on motor torque measurement)
1: Flow meter (based on flow metersensor)
This parameter is related to parameter P9.7-P9.10.
P9.24 M
INIMUM
FLOW
This parameters is the threshold level to determine underload fault when P9.23 = Flow meter.