Description of Groups
vacon • 22
Service support: find your nearest Vacon service center at www.vacon.com
3
3.3.4
Group Digital inputs: Menu PAR G4
Code
Parameter
Min
Max
Unit
Default
ID
Description
P4.1
Start signal 1
0
6*
1
403
Start signal 1 when control
place is I/O 1 (FWD)
See P2.1 for function.
0 = not used
1 = DIN1
2 = DIN2
3 = DIN3
4 = DIN4
5 = DIN5
6 = DIN6
P4.2
Start signal 2
0
6*
2
404
Start signal 2 when control
place is I/O 1 (REV).
See P2.1 for function.
See P4.1 for selections.
P4.3
Reverse
0
6*
0
412
Independent from P2.1
See P4.1 for selections
P4.4
External fault close
0
6*
5
405
Fault if signal high
See P4.1 for selections
P4.5
External fault open
0
6*
0
406
Fault is signal low
See P4.1 for selections
P4.6
Fault reset
0
6*
3
414
Resets all active faults
P4.7
Run enable
0
6*
0
407
Must be on to set drive in
Ready state
P4.8
Preset speed B0
0
6*
4
419
Binary selector for Preset
speeds
P4.9
Preset speed B1
0
6*
0
420
Binary selector for Preset
speeds
P4.14
Sel. control place 2
0
6*
0
1813
Activates control place 2
See P4.1 for selections
P4.15
Sel. freq. reference 2
0
6*
0
1814
Activates reference 2
See P4.1 for selections
P4.16
Sel. PID
setpoint 2
0
6*
0
431
Activates setpoint 2
See P4.1 for selections
P4.17
Mains connected
0
6*
0
1931
Digital input is high when
mains supply is connected
P4.18
Energy counter reset
0
6*
0
1932 Reset of Energy counter
P4.19
Flowmeter pulse
0
6*
5
1953
Digital input for pulse flow
meter (P15.1 = 1)
P4.20
Total flow reset
0
6*
6
1957
Digital input for flow counter
reset
P4.21
Minimum water level
0
6*
0
1963 Digital input for water level
Table 10. Digital inputs group.