vacon • 35
Description of Groups
3
3.3.13
Group Solar: Menu PAR G14
Code
Parameter
Min
Max
Unit
Defau
lt
ID
Description
Start Settings
P14.1
Start DC Voltage
400
800
V
650
1916
DV voltage threshold level to
activate Run enable
P14.2
Short restart delay
0.1
5.0
m
1.0
1917
Delay time to restart
P14.3
Short restart delay tries
1
10
5
1918
Number of restart tries
P14.4
Long restart delay
6.0
30.0
m
10.0
1919
Long delay time to restart
MPPT
P14.5
Vmp at 100% power
400
800
V
600
1920
P14.6
Vmp at 10% power
400
700
V
540
1921
P14.7
Panel/Motor ratio
50.00
100.00
%
100.0
0
1922
P14.8
P gain
0.000
1.000
0.050
1923
Gain for internal PI regulator.
The internal frequency refer-
ence keeps the panels working
on MPP.
P14.9
I gain
0.000
1.000
0.050
1924
Integration time.
P14.10
Acceleration time
0.1
60.0
s
1.0
1925
Time from minimum to maxi-
mum frequency
P14.11
Deceleration time
0.1
60.0
s
1.0
1926
Time from maximum to mini-
mum frequency
P14.12
P&O update time
2
6
s
3
1939
P14.13
P&O voltage step
3
10
V
5
1940
P14.14
P&O power variation
0.2
5.0
%
1.0
1941
P14.15
P&O local max step
0
60
V
30
1945
P14.16
P&O local max time
1
60
m
10
1946
P14.17
P&O local max freq
0.00
20.00
Hz
10.00
1947
P14.18
Damping sensitivity
5
50
V
10
1943
Amplitude of oscillation to be
recognized
P14.19
Damping time
3
10
s
4
1944
Time for the oscillations on DC
voltage
P14.20
Sleep in solar mode
0
1
0
1964
0 = Sleep disabled
1 = Sleep according to P12.12
and P12.13
Table 19. Solar group.
NOTE!
Visibility of the group depends on P1.16.
NOTE!
Sleep in solar mode can be managed according to P12.12 and P12.13
When P14.20 =1, the drive will stop if the output frequency is below the value in
P12.12, for the time in P12.13. It will restart as after a stop due to low power.
Sleep function allows to program a minimum frequency P1.1 that is below the
efficient range of the pump. MPPT can reach this low value, leading to a mini-
mum output power and avoiding to stop the drive in case of temporary reduced
irradiation. If the condition persists, sleep logic will then stop the drive.