9.15 Parameter Settings
Program boiler electronic board parameters as follows:
• Press
and
together, hold them down
for 6 seconds until program “
P01
” appears on the
display alternated with the set value;
• Press
or
to scroll the list of parameters;
• Press
, value of selected parameter begins
flashing, press
to change the value;
• Press
to confirm the value or press
to
exit without saving.
Further information in regards to parameters listed in
the following table are supplied together with required
accessories if necessary.
Parameters continued on next page
For Natural Gas :
Input (MBH)
=
3600 x cu ft
seconds
Example: Natural Gas - Gas flow from
Meter = 2 cu ft
Measured time = 72 seconds
=
3600 x 2 cu ft
= 100 MBH
72 seconds
For Propane (LP):
Input (MBH)
=
9160 x cu ft
seconds
For Metric formulas- See Glossary
2.
Compare measured input to table below. If
calculated input is not in range given in Table 9-2
check firing rate again after setting the combustion
following steps in section 9.12.
Input Rate (MBH)
9 - START UP PROCEDURE
Approximate Rate @
100% Fire (MBH)
Size
100
93.5
115
115
125
125
150
150
165
164
205
205
9.16 Description Of Parameters: Factory Settings
FACTORY
SETTINGS
100,
125,165
115,
150,205
P01
Manufacturer information
01
P02
Gas used
00
= Gas A (Natural Gas)
01
= Gas E (LPG Gas)
00
P03
Hydraulic system
00
= instantaneous appliance
03
= instantaneous appliance with pre-heat function
04
= heating only appliance with DHW thermostat
05
= appliance with external storage indirect tank
08
= heating only appliance
13
= instantaneous appliance with pre-heat function for solar application
08
00
P06
Outdoor temperature sensor input configuration
00
= with outdoor temperature sensor connected, external temperature value has influence to calculate
heating flow temperature set-point
01
= with outdoor temperature sensor connected, display shows external temperature value (no
influence)
02…05
= no function is associated
00
P07
00..02
= No function is associated
03
= This is an input contact for CH request (e.g. trigger phone).
When contact CN2 is closed and Room Thermostat (RT) requiring heat switches burner on.
Note:
verify heating mode is enabled (winter or heat only mode)
04
= This is an input contact for Low Temperature Thermostat (e.g. floor heating system).
When Low Temperature Thermostat connected on CN2 cuts out, burner switches off and display
shows
E178
anomaly.
Note:
verify heating mode is enabled (winter or heat only mode)
05
= This is an input contact for external DHW recirculation pump. When contact CN2 is closed the
pump runs for a specific period.
To enable input it is necessary to set parameter
P04 or P05 = 08
and
P69 = 05
.
Pump will run at
P19
minutes (Summer/Winter mode or Only Winter mode) or
P19/2
minutes
(only Summer mode).
00
P09
Manufacturer information
Default 01
NOTICE
Important!
Record any changes made to
Parameters on chart found on Page 46 of the
Application Guide supplied with your boiler.
Table 9-2 Input Rate @ High Fire (MBH)
240013371 REV B, [10/01/2021]
Содержание MACF-115
Страница 2: ...MACF 150 ...
Страница 4: ...MAHF 125 ...
Страница 74: ...70 A 1 MODEL 100 Heat Only APPENDIX A WIRING DIAGRAMS 240013371 REV B 10 01 2021 ...
Страница 75: ...71 A 2 MODEL 125 Heat Only APPENDIX A WIRING DIAGRAMS 240013371 REV B 10 01 2021 ...
Страница 76: ...72 APPENDIX A WIRING DIAGRAMS A 3 MODEL 165 Heat Only 240013371 REV B 10 01 2021 ...
Страница 77: ...73 APPENDIX A WIRING DIAGRAMS A 4 MODEL 115 Combi 240013371 REV B 10 01 2021 ...
Страница 78: ...74 A 5 MODEL 150 Combi APPENDIX A WIRING DIAGRAMS 240013371 REV B 10 01 2021 ...
Страница 79: ...75 A 6 MODEL 205 Combi APPENDIX A WIRING DIAGRAMS 240013371 REV B 10 01 2021 ...
Страница 80: ...76 NOTES 240013371 REV B 10 01 2021 ...
Страница 81: ...77 NOTES 240013371 REV B 10 01 2021 ...
Страница 82: ...78 NOTES 240013371 REV B 10 01 2021 ...
Страница 117: ...33 MODEL 100 Heat Only 100 HEAT ONLY WIRING DIAGRAM PN 240012875 REV C 10 01 2021 ...
Страница 118: ...34 MODEL 125 Heat Only 125 HEAT ONLY WIRING DIAGRAM PN 240012875 REV C 10 01 2021 ...
Страница 119: ...35 MODEL 165 Heat Only 165 HEAT ONLY WIRING DIAGRAM PN 240012875 REV C 10 01 2021 ...
Страница 120: ...36 115 COMBI WIRING DIAGRAM MODEL 115 Comb PN 240012875 REV C 10 01 2021 ...
Страница 121: ...37 MODEL 150 Combi 150 COMBI WIRING DIAGRAM PN 240012875 REV C 10 01 2021 ...
Страница 122: ...38 MODEL 205 Combi 205 COMBI WIRING DIAGRAM PN 240012875 REV C 10 01 2021 ...
Страница 127: ...43 LOW WATER CUTOFF DETAIL LOW WATER CUTOFF NO NO YES PN 240012875 REV C 10 01 2021 ...
Страница 132: ...48 3 FAULT SOLUTION SECTIONS PN 240012875 REV C 10 01 2021 ...
Страница 135: ...51 Parameter ID Changed From Changed To Date Reason PARAMETER CHANGE HISTORY PN 240012875 REV C 10 01 2021 ...