5 - COMBUSTION AIR AND VENT PIPING
5.8 Twin Pipe Systems
Twin pipe venting allows exhaust flue and intake flue to
be separated from each other. Fresh air is drawn in at a
different area from the flue terminal location.
A.
Twin Pipe CPVC System
CPVC is approved for boiler exhaust. CPVC or PVC are
both approved for air intake.
To transition from Coaxial at the top of the boiler to Twin
Pipe CPVC/PVC a kit is available.
B.
Twin Pipe Polypropylene System
Single wall polypropylene is used for both exhaust and
air intake piping. PVC can be used on
intake only
on
twin pipe applications.
Use the appropriate transition kit to change from
polypropylene to PVC. To transition from Coaxial, at the
top of the boiler to Twin Pipe polypropylene venting an
adapter kit is available.
C.
Twin Pipe Separated Flue
Exhaust and combustion air intake are not located in
same general location.
D.
Twin Pipe - Common Atmospheric Zone
Termination
Exhaust and combustion air intake are located in same
general location and are of equal length.
Grade, Snow
& Ice
Maintain 12"(305 mm) US, 18"(457
mm) Canada clearance above highest
anticipated snow level, 24" (610 mm)
above roof.
Avoid locations where snow may drift
and block vent and combustion air.
Ice or snow may cause boiler to shut
down if vent or combustion air becomes
obstructed.
WARNING
Asphyxiation hazard! Improper installation could
result in death or serious injury. Read Twin
Pipe Installation Instructions completely and
understand all requirements before beginning
installation.
!
FIGURE 5-8 - 2"/60 mm & 3"/80 mm Twin Pipe
Separated Horizontal Flue Termination
This Termination
can be used on:
2" / 60 mm ON
165/205
3" / 80 mm
ON ALL SIZES
vent only
FIGURE 5-9 - 2"/60 mm & 3"/80 mm Twin Pipe
Separated Horizontal Flue Termination
This Termination
can be used on:
2" / 60 mm ON
165/205
3" / 80 mm
ON ALL SIZES
vent only
FIGURE 5-10 - 2"/60 mm & 3"/80 mm Twin Pipe
Separated Horizontal Flue Termination With Tee On
Exhaust - CAN BE USED ON ALL SIZES
This Termination
can be used on:
2" / 60 mm
ON ALL SIZES
3" / 80 mm
ON ALL SIZES
vent only
Twin Pipe Maximum Vent Lengths
(Includes first elbow and termination)
Boiler
100/115/125/150
165/205
All
Vent Size
3"
[80 mm]
2"
[60 mm]
3"
[80 mm]
2"
[60 mm]
All
Maximum
Minimum
Intake
Vent
L1
49 ft
[15m]
85 ft
[25.9m]
100 ft
[30.5m]
85 ft
[25.9m]
6 ft
[1.8 m]
Exhaust
Vent
L2
147 ft
[45m]
Combined
Vent
L1+L2
196 ft
[60m]
170 ft
[51.8m]
200 ft
[60.9m]
170 ft
[51.8m]
12 ft.
[3.6 m]
Single Wall Elbows - Equivalent Length
3" (80 mm)
2" (60 mm)
45° bend
0.82 ft [0.25 m]
3 ft [0.91 m]
90° bend
1.64 ft [0.50 m]
5 ft [1.5 m]
NOTE: Two pipe can be installed horizontally or vertically.
240013371 REV B, [10/01/2021]
Содержание MACF-115
Страница 2: ...MACF 150 ...
Страница 4: ...MAHF 125 ...
Страница 74: ...70 A 1 MODEL 100 Heat Only APPENDIX A WIRING DIAGRAMS 240013371 REV B 10 01 2021 ...
Страница 75: ...71 A 2 MODEL 125 Heat Only APPENDIX A WIRING DIAGRAMS 240013371 REV B 10 01 2021 ...
Страница 76: ...72 APPENDIX A WIRING DIAGRAMS A 3 MODEL 165 Heat Only 240013371 REV B 10 01 2021 ...
Страница 77: ...73 APPENDIX A WIRING DIAGRAMS A 4 MODEL 115 Combi 240013371 REV B 10 01 2021 ...
Страница 78: ...74 A 5 MODEL 150 Combi APPENDIX A WIRING DIAGRAMS 240013371 REV B 10 01 2021 ...
Страница 79: ...75 A 6 MODEL 205 Combi APPENDIX A WIRING DIAGRAMS 240013371 REV B 10 01 2021 ...
Страница 80: ...76 NOTES 240013371 REV B 10 01 2021 ...
Страница 81: ...77 NOTES 240013371 REV B 10 01 2021 ...
Страница 82: ...78 NOTES 240013371 REV B 10 01 2021 ...
Страница 117: ...33 MODEL 100 Heat Only 100 HEAT ONLY WIRING DIAGRAM PN 240012875 REV C 10 01 2021 ...
Страница 118: ...34 MODEL 125 Heat Only 125 HEAT ONLY WIRING DIAGRAM PN 240012875 REV C 10 01 2021 ...
Страница 119: ...35 MODEL 165 Heat Only 165 HEAT ONLY WIRING DIAGRAM PN 240012875 REV C 10 01 2021 ...
Страница 120: ...36 115 COMBI WIRING DIAGRAM MODEL 115 Comb PN 240012875 REV C 10 01 2021 ...
Страница 121: ...37 MODEL 150 Combi 150 COMBI WIRING DIAGRAM PN 240012875 REV C 10 01 2021 ...
Страница 122: ...38 MODEL 205 Combi 205 COMBI WIRING DIAGRAM PN 240012875 REV C 10 01 2021 ...
Страница 127: ...43 LOW WATER CUTOFF DETAIL LOW WATER CUTOFF NO NO YES PN 240012875 REV C 10 01 2021 ...
Страница 132: ...48 3 FAULT SOLUTION SECTIONS PN 240012875 REV C 10 01 2021 ...
Страница 135: ...51 Parameter ID Changed From Changed To Date Reason PARAMETER CHANGE HISTORY PN 240012875 REV C 10 01 2021 ...