31
ACCESSORIES
2. 10K Ω INDIRECT STORAGE TANK SEN
-
SOR KIT
Heating Only boiler can be electrically connected to
Indirect Storage Tank.
Diagram of electrical connection of external indirect
storage tank is shown below.
Connect DHW priority sensor to terminals 3 and 4 on
terminal block M2. The element of the sensor must be
inserted in the sensor well located on the indirect storage
tank.
Verify the exchange capacity of the storage boiler coil is
appropriate for power of the heating only boiler. Adjust
DHW temperature (+95°F...+140°F / +35°C...+60°C) by
pressing
buttons on boiler control panel.
Note
Management of 0-10V Input
P78=1
P78 = 2
Voltage
Temp Setting
100/115
125/150
165/205
°C
°F
kW
MBH
kW
MBH
kW
MBH
0-3
OFF
3
25
77
4.9
16.6
6.4
22.0
8.6
29.5
4
32
90
8.4
28.9
10.7
36.5
14.4
49.0
5
40
104
12.0
40.8
14.9
51.0
19.9
68.0
6
49
120
15.4
52.4
19.2
65.5
25.5
87.0
7
57
135
18.5
63.1
23.4
80.0
31.1
106.0
8
65
149
22.2
75.7
27.7
94.5
36.6
125.0
9
73
163
25.3
86.2
31.9
109.0
42.5
145.0
10
80
176
27.4
93.6
36.9
125.0
48.1
164.0
Parameter PO3 for
Heating Only
boiler, with no
indirect tank remains Factory Set at 08. No change
is required.
If adding an Indirect Tank with a sensor to
Heating Only Boiler
- change PO3 parameter
from 08 to 05.
If adding an Indirect Tank with a thermostat to
Heating Only Boiler
- change PO3 parameter
from 08 to 04.
See Section 9, Parameter Settings, in boiler’s
Installation, Operation, and Maintenance Manual.
Parameter PO3 for
COMBI
boiler factory set at OO
requires no change.
Electrical Connection
Heating Only Boiler
Indirect DHW Tank
End Switch Wiring
(100,125 & 165
MODELS)
Electrical Connection
Heating Only Boiler
10
9
8
7
6
5
4
3
2
1
S
Indirect DHW Tank
Sensor Wiring
(100 & 125 MODELS)
10k Ω
10
9
8
7
6
5
4
3
2
1
To activate the 0-10v function
parameter 82
must be set to
3
.
There must be at or above 3 V DC present for the control to recognize a call for heat.
When
P78 = 1
the 0-10v input manages CH heating setpoint directly per chart below.
When
P78 = 2
the 0-10v input manages CH heating input directly per chart below.
When
P78 = 0
Disabled
PN 240012875 REV. C [10/01/2021]
Содержание MACF-115
Страница 2: ...MACF 150 ...
Страница 4: ...MAHF 125 ...
Страница 74: ...70 A 1 MODEL 100 Heat Only APPENDIX A WIRING DIAGRAMS 240013371 REV B 10 01 2021 ...
Страница 75: ...71 A 2 MODEL 125 Heat Only APPENDIX A WIRING DIAGRAMS 240013371 REV B 10 01 2021 ...
Страница 76: ...72 APPENDIX A WIRING DIAGRAMS A 3 MODEL 165 Heat Only 240013371 REV B 10 01 2021 ...
Страница 77: ...73 APPENDIX A WIRING DIAGRAMS A 4 MODEL 115 Combi 240013371 REV B 10 01 2021 ...
Страница 78: ...74 A 5 MODEL 150 Combi APPENDIX A WIRING DIAGRAMS 240013371 REV B 10 01 2021 ...
Страница 79: ...75 A 6 MODEL 205 Combi APPENDIX A WIRING DIAGRAMS 240013371 REV B 10 01 2021 ...
Страница 80: ...76 NOTES 240013371 REV B 10 01 2021 ...
Страница 81: ...77 NOTES 240013371 REV B 10 01 2021 ...
Страница 82: ...78 NOTES 240013371 REV B 10 01 2021 ...
Страница 117: ...33 MODEL 100 Heat Only 100 HEAT ONLY WIRING DIAGRAM PN 240012875 REV C 10 01 2021 ...
Страница 118: ...34 MODEL 125 Heat Only 125 HEAT ONLY WIRING DIAGRAM PN 240012875 REV C 10 01 2021 ...
Страница 119: ...35 MODEL 165 Heat Only 165 HEAT ONLY WIRING DIAGRAM PN 240012875 REV C 10 01 2021 ...
Страница 120: ...36 115 COMBI WIRING DIAGRAM MODEL 115 Comb PN 240012875 REV C 10 01 2021 ...
Страница 121: ...37 MODEL 150 Combi 150 COMBI WIRING DIAGRAM PN 240012875 REV C 10 01 2021 ...
Страница 122: ...38 MODEL 205 Combi 205 COMBI WIRING DIAGRAM PN 240012875 REV C 10 01 2021 ...
Страница 127: ...43 LOW WATER CUTOFF DETAIL LOW WATER CUTOFF NO NO YES PN 240012875 REV C 10 01 2021 ...
Страница 132: ...48 3 FAULT SOLUTION SECTIONS PN 240012875 REV C 10 01 2021 ...
Страница 135: ...51 Parameter ID Changed From Changed To Date Reason PARAMETER CHANGE HISTORY PN 240012875 REV C 10 01 2021 ...