50
NOTICE
During initial ignition, burner may not ignite. This
may cause boiler to shut down until any air in gas
pipes is vented. Repeat ignition procedure until
gas reaches the burner. To reset boiler operation,
press
for at least 2 seconds.
9.10 De-Aeration Function
Used to eliminate air inside the heating circuit when
boiler is installed or after maintenance when water is
drained from primary circuit.
1.
Press buttons
together and hold for 6
seconds.
On
appears on display for a few seconds,
followed by program row
312
.
2.
The electronic board will activate pump on/off cycle
for 10 minutes. Function will automatically stop at
end of cycle.
3.
To manually exit this function, press
buttons together and hold for 6 seconds.
9.11 Commission Set Up (Gas) - Changing The Type
Of Gas
During the
first
installation boiler carries out an
automatic commissioning function.
The system is able to detect the gas type present in the
network.
Correct gas type setting, is made by pressing two buttons at
the same time, see section 9.6 Commissioning.
Change of gas type is made
after
the first installation:
• Change parameter P02. See section 9.6
Commissioning
and
section 9.15
Parameter
Settings.
• Check minimum gas pressure is suitable for selected gas:
Minimum gas pressure is determined with boiler operating
at high fire and any other appliances connected to same fuel
source operational as well (whole house load)
Gas A (NG) = 3.5" (8.7 mbar)
Gas E (LPG) = 8.0" (19.9 mbar)
• Place supplied label with indication of gas type close
to the data plate of boiler replacing the original.
• Perform Automatic Calibration Function -
Section 9.8.
• Manufacturer recommends
verification of CO
2
concentration on the flue.
FIGURE 9-3 - Gas Inlet Tap - Pi
9 - START UP PROCEDURE
PI
PI = Gas Supply Inlet Pressure Tap
PI
IMPORTANT INFORMATION
A. If gas recognition function is interrupted by power
blackout, start function again when power is
restored. Press
and
together and hold at
same time for at least 6 seconds.
B. If display shows fault
E118
(low pressure in
hydraulic circuit) open filling tap on appliance and
restore correct pressure.
C. If gas recognition function is interrupted due
to fault (e.g.:
E133
no gas) press
to
reset. Then press
and
(for at least
6 seconds) to restart the function again.
If gas recognition function is interrupted due to
overheating, restart function by pressing and
holding down together for at least 6 seconds.
D. Combustion of this appliance has been factory
controlled, calibrated and set for operation with
Gas A
(Natural Gas).
E. During Gas Type Control Function, combustion ratio
will increase for a short period of time while gas
type is being established.
9.9 Manual Calibration Function:
Manual Calibration phase starts at the end of the
Automatic Calibration.
The Display shows the boiler power and adjustment
of the CO2 value (parameter setting) during Manual
Calibration sequence.
The process begins at minimum power.
A. After Automatic Calibration sequence with
flashing together on the display, you can adjust
minimum power combustion by pressing
to
lower % CO
2
, and
to raise % CO
2
.
B. When minimum power combustion is in the
specified range, press
and then
to reach
ignition power.
C. Press
to adjust ignition power combustion.
Press
to lower % CO
2
, and
to raise % CO
2
.
D.
When ignition power combustion is in the specified
range, press
and then
to reach maximum
power.
E. Press
to adjust maximum power combustion.
Press
to lower % CO
2
, and
to raise % CO
2
.
F. When maximum power combustion is in the
specified range,
press
to exit Manual Calibration
Function.
ESC
is displayed on the screen.
240013371 REV B, [10/01/2021]
Содержание MACF-115
Страница 2: ...MACF 150 ...
Страница 4: ...MAHF 125 ...
Страница 74: ...70 A 1 MODEL 100 Heat Only APPENDIX A WIRING DIAGRAMS 240013371 REV B 10 01 2021 ...
Страница 75: ...71 A 2 MODEL 125 Heat Only APPENDIX A WIRING DIAGRAMS 240013371 REV B 10 01 2021 ...
Страница 76: ...72 APPENDIX A WIRING DIAGRAMS A 3 MODEL 165 Heat Only 240013371 REV B 10 01 2021 ...
Страница 77: ...73 APPENDIX A WIRING DIAGRAMS A 4 MODEL 115 Combi 240013371 REV B 10 01 2021 ...
Страница 78: ...74 A 5 MODEL 150 Combi APPENDIX A WIRING DIAGRAMS 240013371 REV B 10 01 2021 ...
Страница 79: ...75 A 6 MODEL 205 Combi APPENDIX A WIRING DIAGRAMS 240013371 REV B 10 01 2021 ...
Страница 80: ...76 NOTES 240013371 REV B 10 01 2021 ...
Страница 81: ...77 NOTES 240013371 REV B 10 01 2021 ...
Страница 82: ...78 NOTES 240013371 REV B 10 01 2021 ...
Страница 117: ...33 MODEL 100 Heat Only 100 HEAT ONLY WIRING DIAGRAM PN 240012875 REV C 10 01 2021 ...
Страница 118: ...34 MODEL 125 Heat Only 125 HEAT ONLY WIRING DIAGRAM PN 240012875 REV C 10 01 2021 ...
Страница 119: ...35 MODEL 165 Heat Only 165 HEAT ONLY WIRING DIAGRAM PN 240012875 REV C 10 01 2021 ...
Страница 120: ...36 115 COMBI WIRING DIAGRAM MODEL 115 Comb PN 240012875 REV C 10 01 2021 ...
Страница 121: ...37 MODEL 150 Combi 150 COMBI WIRING DIAGRAM PN 240012875 REV C 10 01 2021 ...
Страница 122: ...38 MODEL 205 Combi 205 COMBI WIRING DIAGRAM PN 240012875 REV C 10 01 2021 ...
Страница 127: ...43 LOW WATER CUTOFF DETAIL LOW WATER CUTOFF NO NO YES PN 240012875 REV C 10 01 2021 ...
Страница 132: ...48 3 FAULT SOLUTION SECTIONS PN 240012875 REV C 10 01 2021 ...
Страница 135: ...51 Parameter ID Changed From Changed To Date Reason PARAMETER CHANGE HISTORY PN 240012875 REV C 10 01 2021 ...