26
5 - COMBUSTION AIR AND VENT PIPING
FIGURE 5-17 -Twin Pipe Side Wall Vent (Multiple
Appliances)
Vent
12" (305 mm) Min.
Separation
Manufacturer Recommends
Greater Separation
Combustion Air
See Grade,
Snow & Ice
FIGURE 5-19 - (3" / 80 mm ONLY) Twin Pipe Side
Wall Vent
Vent
3" (80 mm) Min.
24" (610 mm) Max.
Separation
12"(305 mm)Min.
From Overhang
12" (305 mm) Min.
24" (610 mm) Max.
Separation Between
Bottom Of
Combustion Air Intake
And Bottom Of Vent
Combustion Air
Opening
Separation 24"
Min.
See Grade,
Snow & Ice
FIGURE 5-18 - (3" / 80 mm ONLY) Twin Pipe Side
Wall with 45° Vent
Vent
45° Elbow
Upward
3" (80 mm) Min.
24" (610 mm) Max.
Separation
Combustion Air, 90°
Elbow Downward
12" (305 mm) Min.
24" (610 mm) Max.
Separation
Opening
Separation 24"
Min.
See Grade,
Snow & Ice
Note: 3" shown for clarity. 12" between
vent and combustion air of other boilers
required in all multiple boiler installations.
FIGURE 5-22 - (2"/ 60 mm ONLY) Twin Pipe Side
Wall Vent CAN BE USED ON ALL SIZES
3" (80 mm) Min.
24" (610 mm) Max.
Separation
See Grade,
Snow & Ice
Combustion Air
Vent
FIGURE 5-20 - (2"/ 60 mm ONLY) Vent Pipe with T
CAN BE USED ON ALL SIZES
See Grade,
Snow & Ice
Combustion Air
Vent
3" (80 mm) Min.
24" (610 mm) Max.
Separation
6" (153 mm) Min.
24" (610 mm) Max.
Separation
FIGURE 5-21 - (2"/ 60 mm ONLY) Vent Pipe with T
CAN BE USED ON ALL SIZES
See Grade,
Snow & Ice
FIGURE 5-23 - (2"/ 60 mm ONLY) Twin Pipe Side
Wall Vent CAN BE USED ON ALL SIZES
Combustion Air
Vent
3" (80 mm) Min.
24" (610 mm) Max.
Separation
See Grade,
Snow & Ice
Vent
Combustion Air
6" (153 mm) Min.
24" (610 mm) Max.
Separation
3" (80 mm) Min.
24" (610 mm) Max.
Separation
This Termination
can be used on:
2" / 60 mm ON
165/205
3" / 80 mm
ON ALL SIZES
vent only
This Termination
can be used on:
2" / 60 mm ON
165/205
3" / 80 mm
ON ALL SIZES
vent only
This Termination
can be used on:
2" / 60 mm ON
165/205
3" / 80 mm
ON ALL SIZES
vent only
240013371 REV B, [10/01/2021]
Содержание MACF-115
Страница 2: ...MACF 150 ...
Страница 4: ...MAHF 125 ...
Страница 74: ...70 A 1 MODEL 100 Heat Only APPENDIX A WIRING DIAGRAMS 240013371 REV B 10 01 2021 ...
Страница 75: ...71 A 2 MODEL 125 Heat Only APPENDIX A WIRING DIAGRAMS 240013371 REV B 10 01 2021 ...
Страница 76: ...72 APPENDIX A WIRING DIAGRAMS A 3 MODEL 165 Heat Only 240013371 REV B 10 01 2021 ...
Страница 77: ...73 APPENDIX A WIRING DIAGRAMS A 4 MODEL 115 Combi 240013371 REV B 10 01 2021 ...
Страница 78: ...74 A 5 MODEL 150 Combi APPENDIX A WIRING DIAGRAMS 240013371 REV B 10 01 2021 ...
Страница 79: ...75 A 6 MODEL 205 Combi APPENDIX A WIRING DIAGRAMS 240013371 REV B 10 01 2021 ...
Страница 80: ...76 NOTES 240013371 REV B 10 01 2021 ...
Страница 81: ...77 NOTES 240013371 REV B 10 01 2021 ...
Страница 82: ...78 NOTES 240013371 REV B 10 01 2021 ...
Страница 117: ...33 MODEL 100 Heat Only 100 HEAT ONLY WIRING DIAGRAM PN 240012875 REV C 10 01 2021 ...
Страница 118: ...34 MODEL 125 Heat Only 125 HEAT ONLY WIRING DIAGRAM PN 240012875 REV C 10 01 2021 ...
Страница 119: ...35 MODEL 165 Heat Only 165 HEAT ONLY WIRING DIAGRAM PN 240012875 REV C 10 01 2021 ...
Страница 120: ...36 115 COMBI WIRING DIAGRAM MODEL 115 Comb PN 240012875 REV C 10 01 2021 ...
Страница 121: ...37 MODEL 150 Combi 150 COMBI WIRING DIAGRAM PN 240012875 REV C 10 01 2021 ...
Страница 122: ...38 MODEL 205 Combi 205 COMBI WIRING DIAGRAM PN 240012875 REV C 10 01 2021 ...
Страница 127: ...43 LOW WATER CUTOFF DETAIL LOW WATER CUTOFF NO NO YES PN 240012875 REV C 10 01 2021 ...
Страница 132: ...48 3 FAULT SOLUTION SECTIONS PN 240012875 REV C 10 01 2021 ...
Страница 135: ...51 Parameter ID Changed From Changed To Date Reason PARAMETER CHANGE HISTORY PN 240012875 REV C 10 01 2021 ...