5 - COMBUSTION AIR AND VENT PIPING
FIGURE 5-16 - Horizontal Twin Pipe, Exhaust and
Intake
12" (305 mm)
Minimum Separation
Manufacturer
Recommends
Greater Separation
Combustion Air
12" (305 mm)
Anticipated Snow Line
Vent - T Terminal
See Grade,
Snow & Ice
Roof
Terminations
12" (305 mm) Min. horizontal separation
between combustion air intake and vent of
same appliance.
12" (305 mm) Min. 84" (2.2 m) Max. vertical
separation between combustion air intake and
vent of different appliances.
15" (381 mm) Max. horizontal length of vent.
Min. vent/intake between different appliances
12" (305 mm).
Max. allowable total vertical vent length with
outside exposure is 10 ft.(3.05 m).
Abandoned unused masonry chimney may be
used as chase-way for combustion air and
vent. Both combustion air and vent pipe must
exit above top of chimney with clearances as
shown in Figure 5-14.
Vent Terminal
Combustion Air
Ground
Level
FIGURE 5-12 - Twin Pipe on Roof Combustion Air On
Sidewall CAN BE USED ON ALL SIZES
FIGURE 5-13 - Twin Pipe Flue On Sidewall,
Combustion Air On Roof CAN BE USED ON ALL SIZES
4
3/4"
[120 mm]
See Grade,
Snow & Ice
FIGURE 5-15 - (3" / 80 mm ONLY) Single Wall
Exhaust Kit and Air Intake Minimum Distance Center
to Center
This Termination
can be used on:
3" / 80 mm
ALL SIZES
vent pipe only
This Termination
can be used on:
2" / 60 mm ON
165/205
3" / 80 mm
ON ALL SIZES
vent only
15"
(381 mm)
Max.
Vent Combustion
Air
12" (305 mm) US,
18" (458 mm) Canada
Min. Above
Anticipated Snow Line
Roof Line
This Termination
can be used on:
2" / 60 mm ON
165/205
3" / 80 mm
ON ALL SIZES
vent only
FIGURE 5-14 - (2"/ 60 mm & 3" / 80 mm) Twin Pipe
Roof Vent CAN BE USED ON ALL SIZES
12" (305 mm) Min.
240013371 REV B, [10/01/2021]
Содержание MACF-115
Страница 2: ...MACF 150 ...
Страница 4: ...MAHF 125 ...
Страница 74: ...70 A 1 MODEL 100 Heat Only APPENDIX A WIRING DIAGRAMS 240013371 REV B 10 01 2021 ...
Страница 75: ...71 A 2 MODEL 125 Heat Only APPENDIX A WIRING DIAGRAMS 240013371 REV B 10 01 2021 ...
Страница 76: ...72 APPENDIX A WIRING DIAGRAMS A 3 MODEL 165 Heat Only 240013371 REV B 10 01 2021 ...
Страница 77: ...73 APPENDIX A WIRING DIAGRAMS A 4 MODEL 115 Combi 240013371 REV B 10 01 2021 ...
Страница 78: ...74 A 5 MODEL 150 Combi APPENDIX A WIRING DIAGRAMS 240013371 REV B 10 01 2021 ...
Страница 79: ...75 A 6 MODEL 205 Combi APPENDIX A WIRING DIAGRAMS 240013371 REV B 10 01 2021 ...
Страница 80: ...76 NOTES 240013371 REV B 10 01 2021 ...
Страница 81: ...77 NOTES 240013371 REV B 10 01 2021 ...
Страница 82: ...78 NOTES 240013371 REV B 10 01 2021 ...
Страница 117: ...33 MODEL 100 Heat Only 100 HEAT ONLY WIRING DIAGRAM PN 240012875 REV C 10 01 2021 ...
Страница 118: ...34 MODEL 125 Heat Only 125 HEAT ONLY WIRING DIAGRAM PN 240012875 REV C 10 01 2021 ...
Страница 119: ...35 MODEL 165 Heat Only 165 HEAT ONLY WIRING DIAGRAM PN 240012875 REV C 10 01 2021 ...
Страница 120: ...36 115 COMBI WIRING DIAGRAM MODEL 115 Comb PN 240012875 REV C 10 01 2021 ...
Страница 121: ...37 MODEL 150 Combi 150 COMBI WIRING DIAGRAM PN 240012875 REV C 10 01 2021 ...
Страница 122: ...38 MODEL 205 Combi 205 COMBI WIRING DIAGRAM PN 240012875 REV C 10 01 2021 ...
Страница 127: ...43 LOW WATER CUTOFF DETAIL LOW WATER CUTOFF NO NO YES PN 240012875 REV C 10 01 2021 ...
Страница 132: ...48 3 FAULT SOLUTION SECTIONS PN 240012875 REV C 10 01 2021 ...
Страница 135: ...51 Parameter ID Changed From Changed To Date Reason PARAMETER CHANGE HISTORY PN 240012875 REV C 10 01 2021 ...