8.- TECHNICAL SUPPORT
- 82 -
SYMPTOM
PROBLEM
SOLUTION
Irregularities are detected in the
measurement.
Machine with residual
charges.
Restart the test
grounding the phases
the recommended time.
Equipment under test is
damaged or has any
insulation failure.
If proper, repeat the test
to secure the fault.
The message: “A SHORT CIRCUIT
EXIST. Check the connection of the
unit with the machine ” appears on
the screen.
The current that circulates
on measurement cables is
very high (delayed
measurement bigger than
3mA) and it is possible that
a short circuit exists in the
machine to measure,
measure connections or
cables of high.
Machine to test:
Damaged machine.
Insulation Resistance is
very low.
Measure connections:
Check that test clamps
are not in short circuit
or that the connections
between bushing and
chassis are properly
insulated.
High voltage Cables:
Check high voltage
cables according to the
section 6.3.
Table 7-1
The numbers in brackets refer to Figure 3-9 (section 3.3).
To contact an authorized technical service or return the equipment, refer to section 8.
Содержание UM2B
Страница 2: ......
Страница 49: ...5 SOFTWARE DESCRIPTION 47 Figure 5 18 Warning message Figure 5 19 a Measurement Screen Recovery Voltage ...
Страница 67: ...5 SOFTWARE DESCRIPTION 65 Figure 5 46 a First page of the report Recovery Voltage ...
Страница 68: ...5 SOFTWARE DESCRIPTION 66 Figure 5 47 a Second page of report Recovery Voltage ...
Страница 69: ...5 SOFTWARE DESCRIPTION 67 Figure 5 48 Third page of report Recovery Voltage ...
Страница 70: ...5 SOFTWARE DESCRIPTION 68 Figure 5 46 b First page of the report Insulation Resistance ...
Страница 71: ...5 SOFTWARE DESCRIPTION 69 Figure 5 47 b Second page of the report Insulation Resistance ...
Страница 87: ...8 TECHNICAL SUPPORT 85 Description of fault Materials returned on of of the year Table 8 1 ...
Страница 95: ...APPENDIX B CONTROL SOFTWARE 93 APPENDIX A CE CONFORMITY DECLARATION ...