8.- TECHNICAL SUPPORT
- 81 -
SYMPTOM
PROBLEM
SOLUTION
On executing the program, the
Test
option is disabled.
The hardware key dongle is
not in place.
Place the key in the
parallel port of the PC,
suitably oriented.
Not has installed the file of
the diskette key
Install
the
program
inserting the diskette
key when concluding
the installation again.
The connecting cable is connected
between the UM2B and the PC, but
the connections screen (Section
5.3.4) indicates the contrary
The series cable is not
properly connected.
Connect properly or
review in
“configuration” if the
COMX port is the
correct one.
The serial cable is
damaged.
Contact an authorized
technical service.
The message: “UM2B does not
respond” appears on the screen
The unit is not turned on.
Turn on the unit.
The serial cable is not
properly connected.
Connect properly or
review in
“configuration” if the
COMX port is the
correct one.
Short-circuit is detected during the
test
Measurement cables are
damaged.
Check measurement
cables.
Equipment under test is
damaged.
If proper, repeat the test
to secure the fault.
Short circuit cables among
phases of every winding are
in contact with chassis or
its isolation is deficient.
Review the wiring.
Irregularities are detected in the
measurement
Short circuit cables among
phases of every winding are
in contact with chassis or
its isolation is deficient.
Review the wiring.
Cables were stepped,
damaged or treaded.
Repeat the test and
check that cables are not
threaded or moved.
Содержание UM2B
Страница 2: ......
Страница 49: ...5 SOFTWARE DESCRIPTION 47 Figure 5 18 Warning message Figure 5 19 a Measurement Screen Recovery Voltage ...
Страница 67: ...5 SOFTWARE DESCRIPTION 65 Figure 5 46 a First page of the report Recovery Voltage ...
Страница 68: ...5 SOFTWARE DESCRIPTION 66 Figure 5 47 a Second page of report Recovery Voltage ...
Страница 69: ...5 SOFTWARE DESCRIPTION 67 Figure 5 48 Third page of report Recovery Voltage ...
Страница 70: ...5 SOFTWARE DESCRIPTION 68 Figure 5 46 b First page of the report Insulation Resistance ...
Страница 71: ...5 SOFTWARE DESCRIPTION 69 Figure 5 47 b Second page of the report Insulation Resistance ...
Страница 87: ...8 TECHNICAL SUPPORT 85 Description of fault Materials returned on of of the year Table 8 1 ...
Страница 95: ...APPENDIX B CONTROL SOFTWARE 93 APPENDIX A CE CONFORMITY DECLARATION ...