5.- SOFTWARE DESCRIPTION
- 61 -
Insulation Resistance Software (ETPRA)
This screen (figure 5-42-b) shows the insulation resistance evolution referred to 20ºC.
taking into account the temperature of the transformer. The field “Temperature” should have
the value entered in “Test configuration” section while in Test phase. This field can be edited
to let the user:
- Compensate to another temperature as the user forgot entering the temperature of
the test or did not know that moment the test temperature. So entering the temperature all
the measurements would appear compensated to that value.
- Take to the screen the real measurement taken by the unit. If the user wishes the
measurement without any compensation, just have to enter the value 20 (20ºC). This way
will get the actual uncompensated temperature.
Insulation Resistance measurement is performed taking one sample each minute in 10
minutes tests and each ten seconds in 1minute last tests.
Figure 5-42-b: Analysis: Graph of insulation resistance (Insulation Resistance SW).
Содержание UM2B
Страница 2: ......
Страница 49: ...5 SOFTWARE DESCRIPTION 47 Figure 5 18 Warning message Figure 5 19 a Measurement Screen Recovery Voltage ...
Страница 67: ...5 SOFTWARE DESCRIPTION 65 Figure 5 46 a First page of the report Recovery Voltage ...
Страница 68: ...5 SOFTWARE DESCRIPTION 66 Figure 5 47 a Second page of report Recovery Voltage ...
Страница 69: ...5 SOFTWARE DESCRIPTION 67 Figure 5 48 Third page of report Recovery Voltage ...
Страница 70: ...5 SOFTWARE DESCRIPTION 68 Figure 5 46 b First page of the report Insulation Resistance ...
Страница 71: ...5 SOFTWARE DESCRIPTION 69 Figure 5 47 b Second page of the report Insulation Resistance ...
Страница 87: ...8 TECHNICAL SUPPORT 85 Description of fault Materials returned on of of the year Table 8 1 ...
Страница 95: ...APPENDIX B CONTROL SOFTWARE 93 APPENDIX A CE CONFORMITY DECLARATION ...