44
……..con2nued
MESSAGE
DESCRIPTION & SOLUTION
LOW BATTERY The baGery voltage dropped below the trip point (10V). The baGery voltage will need to rise
above the recovery voltage before the motor will run again.
♦
Check that the main supply is not switched off or possibly has been leL off for an extended
period of 2me. It can take a flat baGery up to 7 hours to recover.
♦
Ensure the gate moves easily along it’s en2re path. A worn gate, incorrect installa2on, worn
wheels etc will put a strain on the baGery and can cause a low baGery.
♦
If this fault occurs con2nuously and the baGery is older than 1 year it may be a faulty
baGery. Go to the ‘Info’ screen, if the charge current (CHARGE I) is low and the baGery
voltage (BATT V) is high but drops when the operator is triggered the baGery might be
faulty.
♦
Check for loose or corroded baGery terminals .
OBSTRUCTION The controller has detected that the gate has exceeded its running parameters or the gate has
encountered an obstruc2on.
♦
Look for an obstruc2on and remove.
♦
Run the gate in manual override to ensure the gate is moving easily and freely.
♦
Make sure the maximum pull force is not exceeded.
♦
Make sure the gate wheels move freely.
♦
Check the gate rail for stones or s2cks.
♦
Make sure the gate enters and leaves the catch bracket easily.
♦
Check that the baGery is fully charged.
If everything appears in order it may be necessary to adjust the gate force se?ngs. Go to Safety
Se?ngs found under Gate Setup on the LCD screen and adjust the opening and/or closing
forces.
WARNING MESSAGES
MESSAGE
DESCRIPTION
TRIGGER
The operator received a trigger signal.
PEDESTRIAN
The operator received a pedestrian trigger.
LOOP
The operator received a loop trigger.
ACTIVATION IS NOT
POSSIBLE WHEN THERE IS
A BATTERY FAULT
CONDITION
If the baGery voltage is too low, the controller will not ac2vate the gate.
ACTIVATION IS NOT
POSSIBLE WHEN THE
SYSTEM IS IN LOCK OUT
The system is currently in Holiday Lockout. Either the Lockout input, Time Manager
or a remote placed the system in Lockout mode. To operate the controller make
sure it is not being held in lockout by any of these.
ENABLE AUTOCLOSE FIRST
Condo/Mul2 User mode cannot be ac2vated if either Auto Close or Beams Auto
Close is not ac2ve.
DISABLE MULTI USER/
CONDO MODE FIRST
Auto Close cannot be deac2vated while Condo/Mul2 User is ac2ve
.
PLEASE RUN SETUP
WIZARD AGAIN
An ac2on was performed that requires the setup wizard to be run again.
ACTIVATION IS NOT
POSSIBLE WHEN THE LOOP
INPUT IS ACTIVE
While the loop input is held low (either by a loop detector or Time Manager) other
trigger inputs will not close the gate
ACTIVATION IS NOT
POSSIBLE WHEN MULTI
USER MODE IS ACTIVE
While Condo/Mul2 User mode is ac2ve, other trigger inputs will not close the gate.
The gate will only close with the Auto Close se?ng.
AUTO LEARN ACTIVE
The Auto Learn func2on is currently ac2ve allowing the operator to learn new re-
motes. To cancel Auto Learn simply press the joys2ck on the Auto Learn icon in the
Remotes menu.
AUTO CLOSE ACTIVE
Auto Close is currently ac2ve.
Con2nues……...
Содержание HT18/36
Страница 6: ...6 TRITEK CONTROLLER SPECIFICATIONS Con2nues...
Страница 20: ...20 RECEIVER SAFETY BEAM B RECEIVER SAFETY BEAM A MAX LOAD 300mA TWO SETS OF SAFETY BEAMS RELAY OUTPUT...
Страница 21: ...21 RADIO RECEIVER LOOP DETECTOR MAX LOAD 300mA EXTERNAL RADIO RECEIVER LOOP DETECTOR...
Страница 22: ...22 RECEIVER SAFETY BEAM RECEIVER SAFETY BEAM CLOSING SAFETY BEAM RELAY OUTPUT CLOSING SAFETY BEAM FET OUTPUT...
Страница 23: ...23 RECEIVER SAFETY BEAM RECEIVER SAFETY BEAM OPENING SAFETY BEAM FET OUTPUT OPENING SAFETY BEAM RELAY OUTPUT...
Страница 26: ...26 ELECTRIC LOCK 3A MAX MAGNETIC LOCK 500mA max 12V 250mA max 24V ELECTRIC LOCK MAGNETIC LOCK...
Страница 51: ...51 NOTES...