34
Alarm Duraon
This se?ng adjusts the dura2on that the alarm output will remain ac2ve.
Hold Alarm
This se?ng will keep the alarm output ac2vated for as long as an alarm condi2on persists. The alarm
output will only switch off aLer the alarm condi2on is removed and the alarm dura2on 2me has expired.
Rearm Duraon
This se?ng prevents alarm condi2ons from con2nuously retriggering the alarm output. The alarm input
will only rearm aLer the alarm condi2on is removed and the Rearm Dura2on has expired.
Stand Open Time
This function sets the maximum length of time that the gate can stand open before the Gate Open Alarm
function is enabled thereby activating the alarm output. When setting the Stand Open Time, take into
consideration any Auto Close times set and the time required to enter or exit through the gate.
……..con2nued
LOCK SETTINGS
Electric Lock
This function enables the use of an electric lock with the operator (see pg. 26 for wiring diagram).
In the event that power to the gate operator is lost, the gate will remain locked and the electric lock will
have to be opened manually.
Magnec Lock
This function enables the use of a magnetic lock with the operator (see pg. 26 for wiring diagram).
In the event that power to the gate operator is lost, the magne2c lock will automa2cally unlock.
Magne2c locks are not suitable for use with solar powered systems. Magne2c locks draw large amounts
of power which will significantly reduce the number of 2mes the gate operator can be operated during a
power failure.
Enabling the Magnec Lock funcon when using an Electric Lock will result in the Electric Lock being
damaged.
Off When Open
This func2on reduces power consump2on of magne2c locks by switching the magne2c lock off while the
gate is open. The lock will only be switched on again when the gate is closed.
Pre Open Delay
This se?ng is used to create a short delay before the gate opens, during which 2me the lock will unlock.
This should be applied when using an electric lock to prevent the gate opening before the electric lock
has unlocked.
Post Open Delay
This se?ng allows the gate to move away from the ’locked’ posi2on before the locked state is restored
to the lock. It is especially useful for magne2c locks that may pull the gate back if re energized before the
gate has moved far enough away from the locked posi2on.
Pre Close Delay
This se?ng is only used where the gate is locked in the open posi2on and needs to be released prior to
closing.
Post Close Delay
This se?ng keeps the lock unlocked for a short period aLer the gate starts closing. Used with magne2c
locks to prevent the gate from slamming shut while closing if the ‘Off When Open’ se?ng is not selected.
Содержание HT18/36
Страница 6: ...6 TRITEK CONTROLLER SPECIFICATIONS Con2nues...
Страница 20: ...20 RECEIVER SAFETY BEAM B RECEIVER SAFETY BEAM A MAX LOAD 300mA TWO SETS OF SAFETY BEAMS RELAY OUTPUT...
Страница 21: ...21 RADIO RECEIVER LOOP DETECTOR MAX LOAD 300mA EXTERNAL RADIO RECEIVER LOOP DETECTOR...
Страница 22: ...22 RECEIVER SAFETY BEAM RECEIVER SAFETY BEAM CLOSING SAFETY BEAM RELAY OUTPUT CLOSING SAFETY BEAM FET OUTPUT...
Страница 23: ...23 RECEIVER SAFETY BEAM RECEIVER SAFETY BEAM OPENING SAFETY BEAM FET OUTPUT OPENING SAFETY BEAM RELAY OUTPUT...
Страница 26: ...26 ELECTRIC LOCK 3A MAX MAGNETIC LOCK 500mA max 12V 250mA max 24V ELECTRIC LOCK MAGNETIC LOCK...
Страница 51: ...51 NOTES...