![Trox Technik FKR-EU Скачать руководство пользователя страница 99](http://html1.mh-extra.com/html/trox-technik/fkr-eu/fkr-eu_installation-and-operating-manual_1172495099.webp)
A
Shaft wall
B
Shaft wall, installation near the floor
C
Shaft wall, installation near the ceiling
5.1
Dry wall screw
5.6
Screw or steel rivet
7.1
UW section
7.1a
Fold the tab inward or cut it off
7.1b
UW section, nominal sizes:
Æ
nominal width 450 - 800
7.2
CW section
7.10
Optional trim panels
7.13
Double layer cladding, on one side of the metal
stud system
7.14
Reinforcing strip
☐
A
Installation opening
☐
A1
Opening in the metal support structure
(without trim panels:
☐
A =
☐
A1)
*
Closed side of metal section must face the
installation opening
Additional requirements: shaft walls with metal support structure
Shaft wall with metal support structure,
Erecting a wall and creating an installation opening
Erect the shaft wall according to the manufacturer's instructions and create an installation opening, see Fig. 74
–
Provide the installation opening in the metal support structure with support sections.
–
In case of mortar-based installation of fire dampers from nominal size
Æ
nominal width 450, install four addi-
tional sections 7.1b at an angle of 45° in order to reinforce the metal support structure.
Installation opening
☐
A [mm]
Installation type
Nominal size
Æ
nominal width
315
355
400
450
500
560
630
710
800
Mortar-based installation
1
☐
A =
Æ
nominal width + max. 450 mm
☐
A1 =
☐
A + (2
×
trim panels)
1)
Optional trim panels
Installation
Shaft walls with metal support structure > General
Fire damper FKR-EU