Mortar-based installation into a lightweight partition wall, FKR-EU and FK2-EU combined
Fig. 38: Mortar-based installation into a lightweight partition wall, FKR-EU and FK2-EU combined
1a
FKR-EU
1b
FK2-EU up to B
×
H
≤
800
×
400 mm
2.1
Mortar
3.2
Lightweight partition wall with metal support struc-
ture or steel support structure, cladding on both
sides
3.6
Compartment wall or safety wall with metal sup-
port structure, cladding on both sides
Z
Spigot construction 370 mm
Flange construction 342 mm
s2
Spigot construction 40 – 225 mm
Flange construction 80 – 225 mm
Up to EI 90 S
Note on combined installation:
Total fire damper surface area
≤
1.2 m².
The number of fire dampers in an installation opening is limited by their size (B
×
H for FK2-EU and /or
Æ
nominal width for FKR-EU) and the overall area of the fire dampers (1.2 m²).
Alternative installation orientations of side-by-side, under or on top of one another possible. Details are available
upon request.
For installation details FK2-EU, see the installation and operating manual for this fire damper type.
Distance to load-bearing structural elements
≥
40 mm
Installation
Lightweight partition walls > Mortar-based installation
Fire damper FKR-EU
57