Opening the damper blade using the crank handle
Fig. 125: Functional test (without power supply)
DANGER!
Danger due to malfunction of the fire damper.
If the damper blade has been opened by means of
the crank handle (without power supply), it will no
longer be triggered by a temperature increase, i.e. in
the event of a fire. In other words, the damper blade
will not close.
To re-establish its function, connect the power
supply.
Requirement
The damper blade is CLOSED
1.
Insert the crank handle (1) into the opening for the
spring winding mechanism (the crank handle is
clip-fixed to the connecting cable).
2.
Turn the crank handle in the direction of the arrow
(2) to just short of the travel stop.
3.
Then quickly rotate the crank handle by
approx. 90° towards the 'lock' position .
ð
The damper blade remains in the OPEN posi-
tion.
4.
Remove the crank handle.
Closing the damper blade using the crank handle
Fig. 126: Functional test (without power supply)
CAUTION!
Danger of injury when reaching into the fire damper
while the damper blade is moving. Do not reach into
the fire damper while actuating the release mecha-
nism.
Requirement
The damper blade is OPEN
1.
Insert the crank handle (1) into the opening for the
spring winding mechanism (the crank handle is
clip-fixed to the connecting cable).
2.
Rotate the crank handle by approx. 90° towards
the 'unlock' position until a click can be heard.
ð
The damper blade is released and closes.
3.
Remove the crank handle.
Functional test
Fire damper with spring return actuator > Spring return actuator BF...