5.12 Solid wood ceilings
5.12.1
Mortar-based installation into solid wood ceilings
Fig. 98: Mortar-based installation into a solid wood ceiling, suspended or upright
1
FKR-EU
2.1
Mortar
4.5
Solid wood ceiling
7.19
Fire-resistant cladding
9.2
Extension piece or duct
Z
Spigot construction 370 mm
Flange construction 342 mm
–
Up to EI 90 S
Additional requirements: mortar-based installation
into solid wood ceilings
≥
75 mm distance from fire damper to load-bearing
structural elements
≥
200 mm distance between two fire dampers in
separate installation openings
Note:
Structural and fire resistance properties of the ceiling
construction, including the attachment to the con-
crete or any required reinforcement, have to be eval-
uated and ensured by others.
Installation
Solid wood ceilings > Mortar-based installation into solid wood ceil...
Fire damper FKR-EU
127