5.7.4 Dry mortarless installation with installation kit TQ
Timber studs
Fig. 62: Dry mortarless installation into a lightweight partition wall with timber support structure, with installation
kit TQ
1
FKR-EU
2.11
Installation kit TQ (factory assembled)
3.4
Timber stud wall (also timber panel construc-
tions), cladding on both sides
4.1
Solid ceiling slab / solid floor
6.5
Mineral wool (depending on wall construction)
6.13
Mineral wool strips A1,
≤
5 mm thick,
≤
1000°C,
filler as an alternative
7.7
Timber support structure / nogging,
at least 60
×
80 mm (at least 60
×
60 mm with
F60)
7.10
Trim panels, 12.5 mm, fire-resistant
7.11
Trim panels, double layer, 2
×
12.5 mm with
staggered joints, fire-resistant
7.12
Trim panels, wood sheet, max. 12.5 mm,
at least 600 kg/³
7.13
Cladding
7.13a
Cladding, fire-resistant
7.13b
Cladding, wood sheet, at least 600 kg/³
7.14
Reinforcing board of the same material as the
wall
7.17
Trimmers, timber support structure / nogging,
at least 60
×
80 mm (min. 60
×
60 mm with F60)
Z
Spigot construction 370 mm
Flange construction 342 mm
*
Installation near the floor analogous to
**
Cover plate, shortened by others
Up to EI 90 S
Up to EI 60 S
EI 30 S
EI 30 to EI 90 S
Installation
Lightweight partition walls with timber support ... > Dry mortarless installation with installation ...
Fire damper FKR-EU
85
Содержание FKR-EU
Страница 162: ...Fire damper FKR EU 162 ...
Страница 163: ...Fire damper FKR EU 163 ...
Страница 164: ...Fire damper FKR EU 164 ...