5.9.2 Mortar-based installation
Mortar-based installation into shaft wall with metal support structure
Fig. 75: Mortar-based installation into shaft wall with metal support structure
1
FKR-EU
2.1
Mortar
3.7
Shaft wall with metal support structure, cladding
on one side
3.10
Wall without adequate fire resistance rating
4.1
Solid ceiling slab / solid floor
5.1
Dry wall screw
6.5
Mineral wool (depending on wall construction)
7.1
UW section
7.5
Steel support structure (box section)
7.10
Trim panels
7.13.1
Cladding, single-layer, adjusted
7.14
Reinforcing board of the same material as the
wall
9.2
Extension piece or duct
Z
Spigot construction 370 mm
Flange construction 342 mm
*
Installation near the floor analogous to
#
optional
–
Up to EI 90 S
–
EI 30 S
EI 30 S – EI 90 S
Installation
Shaft walls with metal support structure > Mortar-based installation
Fire damper FKR-EU
100