Erecting a wall and creating an installation opening
Erect the shaft wall according to the manufacturer's instructions and create an installation opening with rein-
–
Option A: Create an opening in the cladding and reinforce it along the perimeter.
–
Option B: Provide the installation opening in the metal support structure with support sections. Install four
additional sections at an angle of 45° in order to reinforce the metal support structure.
Fix the cladding and reinforce the installation opening along the perimeter.
Installation opening
☐
A [mm]
Installation type
Nominal size
Æ
nominal width
315
355
400
450
500
560
630
710
800
Mortar-based installation
1
☐
A =
Æ
nominal width + max. 450 mm
☐
A1 =
☐
A + (2
×
trim panels)
1)
Optional trim panels
5.10.2
Mortar-based installation
Mortar-based installation into shaft wall without metal support structure
Fig. 78: Mortar-based installation into shaft wall without metal support structure
1
FKR-EU
2.1
Mortar
3.9
Shaft wall without metal support structure, clad-
ding on one side
4.1
Solid ceiling slab / solid floor
5.1
Dry wall screw
7.1
UW section
7.13
Cladding, double layer, fire-resistant
7.14
Reinforcing board of the same material as the
wall
9.2
Extension piece or duct
Z
Spigot construction 370 mm
Flange construction 342 mm
*
Installation near the floor analogous to
Up to EI 90 S
Additional requirements: mortar-based installation
into shaft walls without metal support structure
Installation
Shaft walls without metal support structure > Mortar-based installation
Fire damper FKR-EU
104