Note on combined installation:
Combined configuration up to 1.2 m² fire damper area.
The number of fire dampers in an installation opening is limited by their size (B
×
H for FK2-EU and /or
Æ
nominal width for FKR-EU) and the overall area of the fire dampers (1.2 m²).
Alternative installation orientations of side-by-side possible. Details are available upon request.
For installation details FK2-EU, see the installation and operating manual for this fire damper type.
Structural properties of the ceiling construction, including the attachment to the mortar/concrete or any required
reinforcement, have to be evaluated and ensured by others.
Minimum number of fixing points in the bare ceiling
H
B
≥
200
≥
500
≥
800
≥
1100
≥
1400
≥
100
4
6
8
10
12
≥
400
6
8
10
12
14
≥
700
8
10
12
14
16
Additional requirements: mortar-based installation
into solid ceiling slab with concrete base
≥
40 mm distance from fire damper to load-bearing
structural elements
If the distance to adjacent solid walls is < 150 mm
and if the concrete base has been correctly
attached, no reinforcement is required on the wall
side.
Concrete bases H
≤
150 mm do not require rein-
forcement
Distance of ≥ 40 mm between two FKR-EU units,
≥ 80 mm for flange construction
Distance to fire dampers FK2-EU
≥
70 – 225 mm
Distance of FKR-EU to a FK-EU 75 – 225 mm
(flange construction 80 – 225 mm)
1.
Screw the fire damper to the existing, dysfunc-
tional fire damper or to the ducting.
2.
Create a concrete base according to Fig. 87 to
3.
Structural and fire resistance properties of the
ceiling construction, including the attachment to
the concrete or any required reinforcement, have
to be evaluated and ensured by others.
Installation
Solid ceiling slabs > Mortar-based installation into a concrete base
Fire damper FKR-EU