5.11.6
Mortar-based installation into hollow stone ceilings
Fig. 91: Mortar-based installation into hollow stone ceilings, shown upright (also applicable for suspended arrange-
ment)
1
FKR-EU
2.1
Mortar
2.2
Concrete
4.8
Hollow stone ceiling*
6.26
Plaster*
7.25
Reinforced concrete support*
9.2
Extension piece or duct
Z
Spigot construction 370 mm
Flange construction 342 mm
Up to EI 90 S
*
Illustration representative, other ceiling construc-
tions possible according to local conditions and
ceiling manufacturers
Additional requirements: mortar-based installation
into hollow stone ceilings
Hollow stone ceiling,
≥
40 mm distance from fire damper to load-bearing
structural elements
≥
200 mm distance between two fire dampers in
separate installation openings
Note:
Structural and fire resistance properties of the ceiling
construction, including the attachment to the con-
crete or any required reinforcement, have to be eval-
uated and ensured by others.
Installation
Solid ceiling slabs > Mortar-based installation into hollow stone ce...
Fire damper FKR-EU
120