Lightweight partition walls with timber support
structure / half-timbered construction
Lightweight partition walls, either timber stud walls
or half-timbered constructions, with European classi-
fication to EN 13501-2 or equivalent national classi-
fication.
Cladding on both sides made of gypsum bonded or
cement bonded panel materials, fibre-reinforced
gypsum or fire-rated calcium silicate boards.
Wall thickness W
≥
130 mm (W
≥
110 for F60,
W
≥
105 for F30); wall thickness of half-timbered
constructions W
≥
140 mm (W
≥
110 for F30).
Erect the timber stud wall or half-timbered construc-
tion according to the manufacturer's instructions.
Additional layers of cladding (if stated in the usability
certificate for the wall) or double stud constructions
are approved.
Create an opening in the timber support structure
with studs and trimmers.
Trim panels and reinforcing boards have to be made
of cladding material and have to be fixed to the
frame at a distance of about 100 mm.
The structural properties of the wall must be
ensured by others and any necessary compensation
measures, especially with large installation open-
ings, must be checked and taken into account by
others.
Solid wood walls
Fire-resistant solid wood walls or cross laminated
timber walls with European or national certificate.
Wall thickness W
≥
95 mm (with reinforcing board
W
≥
100 mm near the installation opening).
If required, additional gypsum bonded or cement
bonded panel materials or fibre-reinforced gypsum
board are permitted.
Shaft walls with metal support structure
Shaft walls or additional leaves with metal support
structure or steel support structure (box sections),
with European classification to EN 13501-2 or equiv-
alent national classification.
Cladding on one side made of gypsum bonded or
cement bonded panel materials, fibre-reinforced
gypsum or fire-rated calcium silicate boards.
Wall thickness W
≥
90 mm (W
≥
75 for F30); clad-
ding / reinforcing boards according to installation
details.
≤
625 mm distance between metal studs.
Be sure to follow the manufacturers' instructions for
the height, width and thickness of walls.
Create an installation opening with trimmers (studs
and noggings).
If necessary, provide trim panels and screw-fix them
to the support structure
Installation is carried out with the actuator on the
outside of the shaft.
If reinforcing boards are required, they must be
screwed to the metal support structure at intervals of
approx. 100 mm.
The structural properties of the wall must be
ensured by others and any necessary compensation
measures, especially with large installation open-
ings, must be checked and taken into account by
others.
Shaft walls without metal support structure
Shaft walls without metal support structure, with
European classification according to EN 13501-2 or
equivalent national classification.
Cladding on one side made of gypsum bonded or
cement bonded panel materials, fibre-reinforced
gypsum or fire-rated calcium silicate boards.
Shaft wall between two solid walls, without corner
formation
Wall thickness W
≥
50 mm.
If reinforcing boards are required, they must be
screwed on at intervals of approx. 100 mm.
Installation
General installation information
Fire damper FKR-EU
35