6
BAS-SVP18D-EN
UC600 Rotary Switches and LEDs
This section provides information about the UC600 rotary switches and LED displays.
Rotary Switches
There are three (3) rotary switches on the front of the UC600. They are used to set the BACnet
MS/TP network address and BACnet Device ID. Refer to the section,
for rules and restrictions with regard to setting this address.
Figure 1. Setting rotary switches
AO
6
UI
14
AO
5
UI
13
AO
4
UI
12
AO
3
UI
11
AO
2
UI
10
AO1
UI
9
BO
4
BO
3
BO
2
BO
1
RELAYS
0.5 A MAX
IMC
1
IMC
P
1
UI
8
UI
7
UI
6
UI
5
UI
4
UI
3
UI
2
UI
1
IMC
+24
VDC
LINK
OUT
+24
VDC
+24
VDC
OUT
24
VAC
MBUS
OUT
24
VAC
XFMR
24
VAC
SERVICE TOOL
SERVICE
LINK
ACT
IMC
MBUS
LINK
RX
TX
UC
600
ADDRESS
0 1
2
3
4
5
6
7
8
9
x1
0 1
2
3
4
5
6
7
8
9
x10
0 1
2
3
4
5
6
7
8
9
x100
BO
4
BO
3
BO
2
BO
1
ADDRESS
0 1
2
3
4
5
6
7
8
9
x1
0 1
2
3
4
5
6
7
8
9
x10
0 1
2
3
4
5
6
7
8
9
x100
Rotary switches after
addresses have been set
IIm
mp
po
orrtta
an
ntt:: Each UC600 device on the BACnet MS/TP link must have a unique rotary switch value
within the range of zero (0) to 127. Otherwise, communication problems will occur.
ADDRESS
0 1
2
3
45
6
7
8
9
x1
0 1
2
3
45
6
7
8
9
x10
0 1
2
3
45
6
7
8
9
x100
Use a 1/8 in. (3 mm) flathead screwdriver
to set rotary switches. Switches rotate
in either direction.
Before
After
LEDs Description, Behavior, and Troubleshooting
There are 14 LEDs on the front of the UC600 device as shown in
.
provides a description of each LED activity, indication, and troubleshooting tips for each, that
includes any specific notes.